3-6. Operating Mode Description
Operating
mode
Description
LCD display
Rack Display
Tower Display
Online
mode
When the input voltage is
within acceptable range,
UPS will provide pure and
stable AC power to output.
The UPS will also charge the
battery at online mode.
ECO mode Energy saving mode:
When the input voltage is
within voltage regulation
range, UPS will bypass
voltage to output for energy
saving. The UPS will also
charge the battery at ECO
mode.
Frequency
Converter
mode
When input frequency is
within 40 Hz to 70 Hz, the
UPS can be set at a constant
output frequency, 50 Hz or
60 Hz. The UPS will still
charge battery under this
mode.
Battery
mode
When the input voltage is
beyond the acceptable range
or power failure, the UPS will
backup power from battery
and alarm is sounding every
5 second.
Bypass
mode
When input voltage is within
acceptable range but UPS is
overload, UPS will enter
bypass mode or bypass
mode can be set by front
panel. Alarm is sounding
every 10 second.
Standby
mode
UPS is powered off and no
output supply power, but still
can charge batteries.