12: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of the UPS.
7-999:
setting the battery total capacity from 7-999 in AH.
Please set the correct battery total capacity if external
battery bank is connected.
13: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the charger maximum current.
For low voltage model with 24/36/48VDC
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8 in
Ampere. (Default: 2A)
For high voltage model with 24/36/48VDC
1/2/4/6/8/10/12:
setting the charger maximum current
1/2/4/6/8/10/12 in Ampere. (Default: 2A)
For low voltage and high voltage model with 72/96VDC
1/2/4/6/8:
setting the charger maximum current 1/2/4/6/8 in
Ampere. (Default: 2A)
Note: Please set the appropriate charger current based on
battery capacity used. The recommended charging current is
0.1C~0.3C of battery capacity as following table for
reference.
Battery capacity(AH)
Total charging current (A)
7~20
2
20~40
4
40~60
6
60~80
8
80~100
10
100~150
12
14: Charger boost voltage setting
Interface
Setting
Parameter 2:
Set up the charger boost voltage.
2.25-2.40:
setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)