3.3. Storage
Please store the UPS in an environment where the temperature is between –15
C +40
C, no
receipt of direct sunlight, far from the heating, in a dry place.
Environmental humidity must be between 30% 90% (non-condensing).
Recommended storage temperature, humidity and altitude values are listed on the
If the batteries will be stored for longer than 6 months, they shall be charged periodically. Charge
period depends on the storage temperature. The relationship is as shown below:
Every 9 months if the temperature is below 20
°
C,
Every 6 months if the temperature is between 20
°
C and 30
°
C,
Every 3 months if the temperature is between 30
°
C and 40
°
C,
Every 2 months if the temperature is over 40
°
C
For long storage duration; please follow up the instructions of installation described in
Section 4
,
start-up UPS described in
Section 7
and charge the batteries at least 12 hours.