PRELImINARY INSTALLATION (continued)
OUTPUT KVA
CONTINUOUS
INPUT
BREAKER SIZE
OUTPUT BREAKER SIZE
MAX OUTPUT CURRENT
75 kVA
300A @ 208V
250A @ 240V
150A @ 480V
100A @ 600V
150A, 3P @ 208V Accelerator
70A, 3P @ 480V BL Generator
60A, 3P @ 480V OBI
30A, 1P @ 120V BL Computers
208/120V 125A Accelerator
480/277V 70A BL Generator
480/277V 55A OBI
120V 25A BL Computers
WEIGHTS, BTU AND DIMENSIONS
OUTPUT KVA
WEIGHT
OPERATIONAL
BTU/HR
TYPICAL
MAXIMUM
BTU/HR
DIMENSIONS
75 kVA
2,194 lbs
995.18 kg
5,115*
10,230
34.5” w x 35.875” d x 76” h
87.63 cm x 91.12 cm x 193.04 cm
* Stated BTU’s / Hr is at 75kVA rated load, 100% duty cycle. Operational BTU’s / Hr is typically at
50% of rated load. Input over current protection provided by others.
**** CAUTION ****
To reduce the risk of fire, use only on circuits provided with ampere
branch circuit protection as noted in the table above, in
accordance with the National Electric Code, ANSI/NFPA 70.
INPUT AND OUTPUT BREAKER SIZE
If unit is provide with no output circuit breaker option, output over-current protection
and a disconnect device (circuit breaker) shall be provided by others.