160K(i) 60 Hz Power Conditioner | Owners Manual
6
PRELIMINARY INSTALLATION
INSTALLATION CONSIDERATIONS
Prior to installing the Series 700AV/T-S, be sure to take into consideration the site you have selected.
Power Conditioners produce heat and therefore require ventilation as well as accessibility. Consider
these factors.
CHOICE OF LOCATION
These units are intended for installation in a temperature-controlled, indoor area free of conductive
contaminants.
The unit has been completely inspected and extensively tested under various load conditions prior to
shipment. Care to install it at a proper location will assure long trouble-free operation.
The unit is air cooled with the air intake at the front and exhausts at the top. Therefore, it should be installed
in a clean, dry place with enough clearance to allow a free flow of air. Allow a minimum of 36” in front of
the 700AV/T-S for installation, operation, and maintenance. There is no clearance required on either the
left or right hand side of this enclosure. Either or both sides, as well as the rear of the enclosure, can be
set flush up against a wall. Input and output conductors should then enter/exit via the top and/or bottom
of the enclosure as indicated.
▪
Ventilation
▪
Input Source Voltage
▪
Size of the Power Conditioner
▪
Receiving Facilities
▪
Weight Load
▪
Distribution of Power
▪
Audible Noise Requirements
▪
Room Temperature
▪
Remote Emergency Power Off (Repo)
▪
Clearances
▪
Monitors
▪
Accessibility
▪
Options
▪
Excessively Long Power Runs
▪
Clean Environment
▪
Proper Ground Techniques
NO CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
NO CLEARANCE REQUIRED
36" CLEARANCE REQUIRED IN FRONT
TOP VIEW
FRONT