INSTALLATION (continued)
INPUT AND OUTPUT CONNECTIONS
1. Input connections are made directly to the unit’s 3 pole main input circuit breaker and input lug provided.
Note the bottom access wire run route illustrated below.
2. Output connections are made directly to the output breaker(s) and output neutral and ground lugs
provided. The load current is not to exceed 80% of the output breaker(s) rating, and not to exceed
the rated total current.
BOTTOM ACCESS WIRE RUN ROUTE
SEPERATION PLATE
OUTPUT METERS
70A 480V
OUTPUT
BREAKER
60A 480V OUTPUT BREAKER
COPPER BUS
OUTPUT TERMINATIONS
TO TOP)
(CUSTOMER'S INPUT CONNECTS
INPUT CIRCUIT BREAKER
SCALE 1 : 2
DETAIL A
BYPASS SWITCH
FRONT VIEW
30A 120V
OUTPUT
BREAKER
150A 208V
OUTPUT
BREAKER
OUT OF RANGE &
MONITOR ALERT
LIGHTS
A
OUTPUT CONDITIONED POWER
INPUT OUT OF RANGE
ALERT
C
B
A
WIRE RANGE: 6 AWG - 250 MCM
INPUT GROUND LUG (1) TA 250