INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

SE5M24

1

Valve actuator for 0(2)...10 V control

SE5M24 is a valve actuator designed for control of AB Industriet-
echnik valves (VFG2, VFG3, VFD2, VFD3, VFDH up to DN80). The 
actuator has automatic self stroke adjustment and can be operated 
manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

 

 

or 24 V DC ±15 % 

Control signal 

 

0(2)...10 V DC 

Power consumption 

Max. 4.5 W 

Stroke 

 

10...30 mm 

Stroke time 

 

1.5 s/mm 

Force 

 

500 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions (WxHxD) 

150 x 253 x 85 mm 

Protection class   

IP54

Installation

If the valve stem adaptor and valve throat adaptor are not already mount-
ed on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the locking bolt (U-bolt) from the actuator yoke. Insert the valve 
stem into the yoke and make sure that the stem adaptor engages the hole 
in the angled iron of the actuator drive spindle.
The groove in the valve throat adaptor must be made to line up with the 
U-bolt mounting holes on the actuator. If the spindle needs moving in or 
out for this to happen, depress the central part of the manual button and 
turn it clockwise for the actuator spindle to extend, and anti-clockwise for 
it to retract (see Manual override). When the valve is in the correct posi-

tion, insert the U-bolt. Tighten the bolt nuts until the valve is firmly gripped. 

Disassembly in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and endpoint calibration

Stroke and endpoint calibration is not necessary due to a construction 
utilizing endpoint stops. When the valve reaches the endpoint, a force is 

generated. Once the force of the actuator reaches a predefined level, the 

limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are five DIP switches for setting different functions. Follow the 

table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

1 (On)

0 (Off)

SW1

Spindle down when the 
valve is closed

Spindle up when the valve is 
closed (FS=factory setting)

SW2

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW3

Reverse operation

Direct operation (FS)

SW4

Y signal split in accordance 
with the setting of SW5

No split function (FS)

SW5

5(6)...10 V = 0...100 %

0(2)...5(6) V = 0...100 % (FS)

SW1 Operational direction of the valve

On:  The valve is closed when the stem is in its lowest position. 

SE5M24

 

11915B OCT

 15

EN

Содержание SE5M24

Страница 1: ...V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and endpoint calibration Stroke and endpoint calibration is not necessary due to a construction utilizing endpoint stops When the valve reaches the endpoint a force is generated Once the force of the actuator reaches a predefined level the limit switch automatically halts the drive motor Override Activation of the ov...

Страница 2: ...o the requirements of the EMC Directive 2004 108 EC through product standards EN 60730 1 2000 and EN 60730 2 14 1997 RoHS This product conforms with the Directive 2011 65 EU of the European Parliament and of the Council Contact AB Industrietechnik Srl Via Julius Durst 70 39042 Bressanone BZ Italy Tel 39 0472 830626 Fax 39 0472 831840 www industrietechnik it info industrietechnik it i ISTRUZIONI SE...

Страница 3: ...ove impostazioni saranno valide a partire dalla successiva accen sione dell attuatore 1 On 0 Off SW1 Perno in basso con valvola chiusa Perno in alto con valvola chiusa FS impostazione di fabbrica SW2 Y 2 10 V CC Y 0 10 V CC FS SW3 Funzionamento inverso Funzionamento diretto FS SW4 Segnale Y suddiviso secon do impostazione di SW5 Nessuna funzione di suddivisione FS SW5 5 6 10 V 0 100 0 2 5 6 V 0 10...

Страница 4: ...e consommée 4 5 W max Course 10 30 mm Temps de course 1 5 s mm Force 500 N Température ambiante 0 50 C Température de stockage 40 80 C Humidité ambiante 10 90 HR Dimensions LxHxP 150 x 253 x 85 mm Indice de protection IP54 Installation Si ce n est pas déjà fait montez la tige et l adaptateur sur la vanne Tirez la tige au maximum Retirez l attache en U de l actionneur Insérez la tige de la vanne da...

Страница 5: ... actionneur ferme la vanne quand le signal de commande augmente Off Fonctionnement direct L actionneur ouvre la vanne quand le signal de commande augmente SW4 Fonction split On Fonction split active Deux actionneurs peuvent partager un même signal de commande et travailler en séquence Off Fonction split inactive SW5 Plage de fonctionnement avec la fonction split On 5 10 V 0 100 6 10 V quand SW2 On...

Страница 6: ...ler U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Hubweg und Enpunktkalibrierung Eine Hubweg und Endlagenkalibrierung wird nicht benötigt da bei Erreichen der Endlage eine Stellkraft generiert wird Erreicht diese ein vorbestimmtes Niveau stoppt ein Endlagenschalter automatisch den Antriebsmotor Übersteuerung Bei Aktivierung des Übersteuerungseingangs wird das Ve...

Страница 7: ...nstellungen während des Testlaufs geändert Die neuen Einstellungen sind ab dem nächsten Einschalten gültig Stetiges rotes und grünes Licht Endlage erreicht Rotes langsam blinkendes Licht Betriebsmodus Übersteuerung Stetiges rotes Licht Fehlfunktion entweder inkorrekte Installation oder fehlender Hubweg Endlagenanzeige An der Konsole des Stellantriebs befinden sich eine rote und eine blaue Endlagen...

Отзывы: