background image

CTR25

2

For slow temperature changes i. e. room control CTR25 will act as a P 
controller with a proportional band of 1.5K.

External control signal

CTR25 can also be run against a 0 - 10V DC control signal from another 
controller.
Remove the wire strap between terminals 7 and 9 and connect the control 

signal as shown in figure 7.

    

0-10V DC in

Signal neutral

8 9

7

Remove 

wire

 

Figure 7: Wiring of external control signal

0V input signal will give 0% output and 10V input will give 100% output. 
Minimum and maximum limit functions are not active when using an 
external control signal.

Start-up and fault finding

1.  Check that all wiring is correct and that the sensor selector switches 

are in the correct position. 

2.  Measure the resistance between terminals L1out - L2out, L1out - 

L3out and L2out -L3out:  
At 230V phase-phase voltage: 10.6

<R<66.4

.  

At 400V phase-phase voltage: 18.4

<R<115

3.  Connect supply voltage and turn the setpoint knob to the maximum 

value. The LED on the CTR25 should be continuously on or pulse 
on/off with longer and longer ontime and eventually be continu-
ously on.Turn the setpoint to the minimum value. The LED should 
be continuously off or pulse on/off with longer and longer offtime 
and eventually be continuously off. At a certain position (within the 
proportional band) the LED will pulse On-Off as the CTR25 pulses 
current to the heater. The pulse cycle period is approx. 6 -60 sec-
onds depending on the setting of the CT-potentiometer. Check with a 

clamp-on ammeter that current is flowing to the heater.

Something wrong?

1.  Remove wiring to external sensor (and setpoint if any). Measure the 

resistance of the sensor and setpoint separately

The potentiometer 

resistance varies 0-  5k

Ω 

between the lower and upper end-point. 

The sensor resistance varies between 10k

 and 15k

 between the 

upper and lower ends of the sensor temperature range. I.e. a STCC-

NTC15-01 has 15k

 at 0°C and 10k

 at 30°C. The resistance 

changes by 167

/°C. 

2.  Leave the sensor terminals unconnected. Set all switches in the 

downward position. Switch the voltage on. 
CTR25 should give full uninterrupted power and the LED should 

be lit. Check with a clamp-on ammeter that current is flowing to 

the heater. 

If the LED is not lit and no current is flowing: Check that you 

have power on terminals L1in, L2in and L3in and recheck the 
positions of the sensor selector switches. If OK the CTR25 is 
probably faulty. 

If the LED lights up but no current is flowing: Recheck the heater 

resistance as above. If OK the CTR25 is probably faulty. 

3.  Shut off power and short-circuit the sensor input 1 and 4. Switch 

on power again. 
CTR25 should not give out any power at all and the LED should 
be extinguished. Check with a clamp-on ammeter that no current 

is flowing to the heater.

 

If the LED is extinguished but current is flowing to the heater the 

CTR25 is faulty. 
If the LED is lit, recheck the shorting of the sensor input termi-
nals. If OK the CTR25 is faulty. 

4.  If everything is OK this far the CTR25 and the sensor/setpoint 

are OK. Shut off power, remove the wire strap from the the 
sensor input terminals and reconnect external sensor(s) (and 
setpoint if any).Set the switches to their correct positions. Con-
nect power.

Low Voltage Directive (LVD) standards

This product conforms to the requirements of the European Low Volt-
age Directive (LVD) 2006/95/EC through product standard EN 60730-
1.

EMC emissions & immunity standards

This product conforms to the requirements of the EMC Direc-
tive 2004/108/EC through product standards EN 61000-6-1 and 
EN 61000-6-3.

RoHS

This product conforms with the Directive 2011/65/EU of the European 
Parliament and of the Council.

Contact

AB Industrietechnik Srl

Via Julius Durst, 70 - 39042 Bressanone (BZ) - Italy
Tel.  +39 0472/830626 - Fax +39 0472/831840
www.industrietechnik.it - [email protected]

Limiting sensor

Terminals 5 and 6. Low voltage. Not polarity sensitive.
When running room temperature control the supply air temperature 
can be limited to a maximum and/or a minimum. The limiting sensor is 
placed in the supply air duct after the heater.
Choice of function is made using switches 2 and 3. Choice of limiting 
temperatures is made on potentiometers Min and Max.

    

STCC-NTC15-02

5 6

 
Figure 6: Wiring of limiting sensor

 

N.B.

 As limiting sensor STCC-NTC15-02 must be used.

Settings

Potentiometers

Setp.  Setpoint 0 - 30°C.
Min 

Minimum limit for supply air temperature when running room  

 

temperature control.

Max 

Maximum limit for supply air temperature when running room  

 

temperature control.

CT 

Cycle time. 6 - 60 seconds.

Switches

Down = External setpoint in use.

 

Up = Internal setpoint in use.

Down = Minimum limit not active.

 

Up = Minimum limit active.

Down = Maximum limit not active.

 

Up = Maximum limit active.

N.B. 

Minimum and maximum limiting functions may be used  

separately or at the same time.

Control principle

CTR25 pulses the full load On - Off. CTR25 adjusts the mean power 
output to the prevailing power demand by proportionally adjusting the 
ratio between On-time and Off-time. The cycle time (=the sum of On-
time and Off-time) is adjustable 0 - 60 seconds.

CTR25 has zero phase-angle firing to eliminate RFI.

CTR25 automatically adapts its control mode to suit the dynamics of 
the control object .
For rapid temperature changes i. e. supply air control CTR25 will act 
as a PI controller with a proportional band of 20K and a reset time of 
6 minutes.

Содержание CTR25

Страница 1: ...s L1in L2in and L3in Supply voltage 210 255 or 380 415V AC 3 phase 50 60 Hz with automatic voltage adaption Maximum current 25A phase N B The supply voltage to CTR25 should be wired via an all pole switch with a minimum contact gap of 3mm N B CTR25 must be earthed 1 1 1 3 2 3 4 5 6 7 8 9 L1 L2 L3 L3 L2 L1 Figure 1 Wiring of supply voltage and load Load Terminals L1out L2out and L3out Resistive 3 p...

Страница 2: ...and 4 Switch on power again CTR25 should not give out any power at all and the LED should be extinguished Check with a clamp on ammeter that no current is flowing to the heater If the LED is extinguished but current is flowing to the heater the CTR25 is faulty If the LED is lit recheck the shorting of the sensor input termi nals If OK the CTR25 is faulty 4 If everything is OK this far the CTR25 an...

Страница 3: ...5 6 7 8 9 L1 L2 L3 L3 L2 L1 Figura 1 Cablaggio del segnale di controllo Carico Morsetti L1out L2out e L3out Riscaldatore resistivo trifase senza neutro Carico massimo 3300W per fase a 230V di tensione fase fase 25A 5750W per fase a 400V di tensione fase fase 25A Carico minimo 530W per fase a 230V di tensione fase fase 4A 920W per fase a 400V di tensione fase fase 4A Sensore principale e setpoint e...

Страница 4: ...ale il LED si accenderà e si spegnerà quando il CTR25 invia corrente al riscaldatore Il periodo del ciclo di impulsi è compreso tra 6 e 60 secondi circa a seconda dell impostazione del potenziometro CT Con una pinza amperometrica controllare il flusso di corrente nel riscaldatore Qualcosa non va 1 Rimuovere il cablaggio del sensore esterno e del setpoint remoto se presente Misurare la resistenza d...

Страница 5: ...au Montieren Sie den CTR25 auf einer DIN Hutschiene in einem Schaltschrank oder Ähnlichem Montieren Sie den CTR25 vertikal sodaß der Text zu lesen ist Schutzklasse IP20 Umgebungstemperatur 0 40 C Beachte Der CTR25 erzeugt ca 45W Abwärme die abgeführt werden muß Verdrahtung Versorgungsspannung Klemmen L1in L2in und L3in Versorgungsspg 210 255 oder 380 415V AC 3 Phasen 50 60 Hz mit aut Spannungsangl...

Страница 6: ...mit einem Zangenamperemeter ob der Strom auch durch die Last fließt Fehlersuche 1 Entfernen Sie die Verdrahtung zum ext Fühler und Sollwertpoti Messen Sie den Widerstand des Fühlers und des Potis sepperat Der Potiwiderstand variiert zwischen 0 5kΩ Der Fühlerwiderstand variiert zwischen 10kΩ und 15kΩ z B ein STCC NTC15 01 hat 15kΩ bei 0 C und 10kΩ bei 30 C Der Wider stand ändert sich mit 167Ω C 2 L...

Страница 7: ... NOTE le CTR25 doit être raccordé à la terre Charge Bornes L1ut L2ut et L3ut Réchauffeur résistif triphasé sans connexion au neutre Charge max 3300W phase pour une tension principale de 230V 25A 5750W phase pour une tension principale de 400V 25A Charge min 530W phase pour une tension principale de 230V 4A 920W phase pour une tension principale de 400V 4A Sonde principale et consigne externe fig 2...

Страница 8: ...Haut limite inf activée 3 Bas limite sup désactivée Haut limite sup activée NOTE les fonctions de limitation min et max peuvent être utilisées ensemble ou séparément Principe de régulation Le CTR25 pulse toute la puissance connectée Le CTR25 adapte la puissance moyenne à la puissance souhaitée en faisant varier progressivement la longueur des impulsions La période de répétition des impulsions somm...

Отзывы: