CMF5U

3

 

The display menu system

The display menu system is divided into two levels, the configuration 
level (10-second level) and the basic level.

The configuration level (10-second level)

This level is reached from the Base Display (see the section 

The 

basic level

 below) by holding the encoder button depressed for 10 

seconds. The 10-second level holds all the configuration menus. 
Note: The controller must display the Base Display when pressing the 
encoder knob to reach the 10-second level.

Table 2 below shows how the 10-second level is organised. When 
you enter the 10-second level, you will see menu level 0. Here, you 
choose the control mode. You navigate through the menus and con

-

trol modes by turning and clicking on the encoder knob. 

Table 2. Display menus in the 10-second level

Menu 

level

Control modes

0

1

2

3

4

5

1

Output 

signal

Transmitter 

range UI1

Transmitter 

range UI1

Transmitter 

range UI1

Transmitter 

range UI1

2

Neutr. zone

-

Neutr. zone

-

-

3

P-band

P-band

P-band

P-band

P-band

4

I-time

I-time

I-time

I-time

I-time

5a

Damper 

min.position

Output min. 

limitation

-

-

-

5b

Output max. 

limitation

-

-

-

6

Tempera

-

ture scale

-

-

-

-

7

-

-

-

-

-

8

-

-

-

-

-

9a

-

-

-

-

Startpoint 

for outdoor 

compen-

sation

9b

-

-

-

-

Max. com

-

pensation

E

External 

setpoint

11

I/O

I/O

I/O

I/O

I/O

Choose control mode in menu level 0 by clicking on the knob so the 
“Menu holds changeable values” symbol (see the section 

Display symbols

 

below) starts flashing, and then turning the knob. When the control mode 
you want to choose is displayed, click once more on the knob so that the 
symbol “Menu holds changeable values” ( ) stops flashing.
When you have chosen the control mode, you move between the menu 
levels by turning the knob when the symbol “Menu holds changeable 
values” ( ) is not flashing.
In some cases, making a certain choice in one menu will mean that you 
will only see certain other menus.

Example: 

To set the I-time for control mode 3 (General control), go to 

menu 3.4. Click on the encoder knob. The symbol “Menu holds change

-

able values” ( ) will start flashing. Change the value by turning the knob 
and confirm the change by clicking on the knob.

 

To exit the 10-second level, go to menu level 12 (Menu OK), and click 
on the encoder knob. You will be returned to the basic level (see below). 
There is also a time-out function that will automatically exit the configura

-

tion level after 5 minutes of inaction.

Storage of settings

All configuration settings become valid as soon as they are entered 
by clicking the encoder knob. They are however not written to the 
flash memory until you exit the configuration level either via the OK 
menu or via the time-out function.
To exit the configuration level without saving the changes to flash 
memory, cut the supply voltage when still in the configuration level. All 
values will be kept as they were before you entered the configuration 
level.

See the “CMF5U Manual” for more information about the  

configuration menus in the 10-second level. 

The basic level

The Base Display is shown when there is no operator activity. 

I/O: 

By turning the knob counter clockwise when the Base Display is 

shown, until the text I/O is displayed, and then clicking on the knob, 
you can access a menu where you can look at the values and states 
of all the inputs and outputs. To exit this menu, click on the knob and 
then turn it clockwise and you will be returned to the Base Display. 

Setpoint: 

When in the Base Display, a click on the encoder button 

gives direct access to the Setpoint menu. To change the setpoint, 
click on the encoder knob again. The symbol “Menu holds change

-

able values” ( ) will start flashing. Change the value by turning the 
knob and confirm the change by clicking on the knob.

External setpoint

Starting with revision R18, it is possible to either use an external 
PT1000 setpoint device or to set the setpoint value via the display. 
External setpoint can only be used for control mode 1 (temperature 
control), and then between 0...40°C. For choice of internal or external 
setpoint, go to menu 1.E, set EXT SP to ON for external setpoint or 
OFF for internal. When using an external setpoint device, you can 
only see the current setpoint in the setpoint menu. When using an 
external setpoint device, the temperature range should therefore be 
set to the lowest area.

Содержание CMF5U

Страница 1: ...500 kPa Neutral zone 12 5 of max P band CO2 0 100 of UI1 General RH 0 100 of UI1 Pressure Pa 0 300 of UI1 I time 0 990 s Control setting 5 Outdoor compens start 20 60 C Setpoint pressure at 20 C outdoor temp 0 Pa 2500 kPa Installation CMF5U must be mounted in a DIN standard casing minimum 7 modules or in a cabinet either on a DIN rail or using the two screw pockets provided by being screwed to any...

Страница 2: ...tput signals on AO1 and AO2 AO1 is used for negative control AO2 for positive control A single PI control loop is used If you want to max limit the humidity connect a DBKH 10H humi distat in series with the start signal to terminals 41 and 42 24 V AC Start signal Humidity transmitter Humidifier Dehumidifier DBKH 10H Max limiting humidistat G G0 DI DI1 UI UI1 AGND AI1 SPI 1 2 3 41 42 43 44 50 51 52...

Страница 3: ...y turning the knob and confirm the change by clicking on the knob To exit the 10 second level go to menu level 12 Menu OK and click on the encoder knob You will be returned to the basic level see below There is also a time out function that will automatically exit the configura tion level after 5 minutes of inaction Storage of settings All configuration settings become valid as soon as they are en...

Страница 4: ...ouncil Contact AB Industrietechnik Srl Via Julius Durst 70 39042 Bressanone BZ Italy Tel 39 0472 830626 Fax 39 0472 831840 www industrietechnik it info industrietechnik it i Prima dell installazione e del cablaggio del prodotto leggere le presenti istruzioni ISTRUZIONI CMF5U In tutti i casi in cui viene utilizzato il simbolo con sultare la documentazione per individuare la natura dei potenziali ri...

Страница 5: ...antita dal dispositivo Modalità di controllo Il CMF può essere configurato per le modalità di controllo descritte di seguito 1 Controllo temperatura La temperatura viene mantenuta al valore di setpoint mediante il controllo dei segnali di uscita su AO1 e AO2 Il setpoint può essere impostato direttamente dal display o tramite un dispositivo di setpoint esterno Viene utilizzato un singolo loop di co...

Страница 6: ...to il livello menu 0 nel quale è possibile selezionare la modalità di controllo Per spostarsi tra i menu e le modalità di controllo ruotare e premere la manopola Tabella 2 Menu visualizzati sul display nel livello 10 secondi Livello menu Modalità di controllo 0 1 2 3 4 5 1 Segnale di uscita Scala di lavoro ingresso UI1 Scala di lavoro ingresso UI1 Scala di lavoro ingresso UI1 Scala di lavoro ingre...

Страница 7: ...lo interno Se si utilizza un dispositivo di setpoint esterno è possibile vedere il setpoint corrente solo nel menu di setpoint Se si utilizza un dispositivo di setpoint esterno è necessario impostare la scala di lavoro di temperatura sull intervallo più basso 20 60 C Menu di configurazione Menu I O selezionando SPI selezione setpoint esterno viene visualizzato il valore effettivo o interno Setpoin...

Страница 8: ...n CMF KIT Le régulateur doit être connecté à un transformateur d isolation de sécu rité 24 V AC qui assure l isolation principale Voir le tableau 1 pour les raccordements Table 1 Borniers de raccordement des E S Les borniers 2 20 et 50 sont tous connectés entre eux Borne Désignation Fonction 1 G Alimentation 24 V AC 2 G0 3 20 AGnd Référence pour AO1 et AO2 21 AO1 Sortie 0 10 V 22 AO2 Sortie 0 10 V...

Страница 9: ... la sortie AO1 Une seule boucle PI est utili sée Le signal AO1 inversé est reçu de AO2 24 V AC Signal de démarrage transmetteur de pression 0 10 V Variateur de fréquence Pa G G0 DI DI1 UI UI1 AGND AI1 SPI 1 2 3 41 42 43 44 50 51 52 20 21 22 AGND AO1 AO2 G0 G Y AO1 signal inversée Figure 4 Exemple de câblage Contrôle de pression 5 Contrôle de pression avec compensation de la température extérieure ...

Страница 10: ... configuration sans sauvegarder les changements dans la mémoire flash coupez l alimentation de l CMF alors que vous trouvez toujours dans le mode configuration Le régulateur revient alors automatiquement aux dernières valeurs sauvegardées avant que vous ne fassiez les modifications Voir le manuel CMF5U Manuel pour en savoir plus sur les menus de configuration Niveau de base Ecran de bienvenue C es...

Страница 11: ...r Er verfügt über 5 Ein Ausgänge und kann so konfiguriert werden dass er Temperatur CO2 relative Feuchte oder Druck regelt Sämtliche Einstel lungen und Konfigurationen werden über das Display und den Drück drehknopf direkt am Regler ausgeführt Ab Version R18 kann ein externer Sollwertgeber mit PT1000 Kennlinie angeschlossen werden Technische Daten Versorgungsspannung 24 V AC 15 50 60 Hz Stromverbr...

Страница 12: ...sgangssignals AO1 auf dem Sollwert gehalten Ein PI Regelkreis wird verwendet Eine min max Begrenzung des Ausgangs ist möglich 24 V AC Klappe Frequenz umrichter CO2 Transmitter G G0 DI DI1 UI UI1 AGND AI1 SPI 1 2 3 41 42 43 44 50 51 52 20 21 22 AGND AO1 AO2 G0 G Y G0 G Y 20 21 22 AGND AO1 AO2 0 10 V Abb 2 Klemmenbelegung CO2 Regelung mit Klappen oder Frequenz umrichter 3 Universalregler Der Istwert...

Страница 13: ...n Werten hört auf zu blinken Wurde der Regelmodus ausgewählt und das Symbol Menü mit veränder baren Werten blinkt nicht mehr kann durch Drehen des Knopfes zwischen den Menüebenen gewechselt werden In einigen Fällen werden durch bestimmte Eingaben in einem Menü nicht alle weiteren Menüs gezeigt Beispiel Um die I Zeit im Regelmodus 3 Universalregler einzustel len muss Menü 3 4 eingestellt werden Den...

Страница 14: ...hrzeigersinn angezeigt Displaysymbole Konfigurationsmenü Menünummer Säulendiagramm Ausgangsleistung AO1 Säulendiagramm Ausgangsleistung AO2 Graphisches Ausgangssignal AO2 nur Regelmodus 1 Graphisches Ausgangssignal AO1 nur Regelmodus 1 Aktives 0 10V Eingangssignal Temperaturregelung Außentemperaturgeführte Regelung konfiguriert Menü mit veränderbarenWerten Change over Zurücksetzen auf Werkseinstel...

Отзывы: