The discharge is ended because of too low flow.
Verify that the unit is filled up with water at start up.
- Verify that both pumps are working at startup.
- Clean the hoses and the pump located in the water.
Verify that water is coming out of the grey and red hose at startup.
- Locate where the water is stopped and clean.
Examine the flowmeter and its connector.
Discharge ended because of failed leakage test. Locate the leakage by checking where water comes
out during leakage test. Commonly, the leakage is at one of the solenoid valves or a hose that is not
firmly connected.
The discharge is ended 2 minutes after startup. Usually there is oil in the water; 5ppm is five
teaspoons in one kbm of water.
Check the status of the pit, the water should be clear. Water that is colored by for example dust
or sand cannot be properly evaluated by the measuring cell. Install a prefilter to solve the
problem. Contact Industriarmatur for support.
Check the status of the filter.
If the SIPP Node does not start, make sure that the SIPP Node 400 is connected to the main power and
that
all
start criteria are met.