Ref. IS.MDUINO.58+ 

 

Rev. 0: 30-08-2019 

 

29 

 

 

Switch Configuration 

8

8.1

 

A Zone: Communications  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. SCL/I2.6: Choosing between SCL or the input I2.6. If this switch is ON, it enables the I2.6    
input and disables the SCL. If this switch is OFF, it enables SCL and disables I2.6.  

3. SDA/I2.5: Choosing between SDA or the input I2.5. If this switch is ON, it enables the I2.5    
input and disables the SDA. If this switch is OFF, it enables SDA and disables I2.5.  

2. RX1/I1.6: Choosing between RX1 or the input I1.6. If this switch is ON, it enables the I1.6    
input and disables the RX1. If this switch is OFF, it enables RX1 and disables I1.6.  

1. TX1/I1.5: Choosing between TX1 or the input I1.5. If this switch is ON, it enables the I1.5    
input and disables the TX1. If this switch is OFF, it enables TX1 and disables I1.5. 

LEFT ZONE 

Switch 

Analog Shield 

Relay Shield 

 

ON 

OFF 

ON 

OFF 

D ZONE 

SCL/I2.6 

I2.6 

SCL 

I2.1 

SCL 

SDA/I2.5 

I2.5 

SDA 

I2.0 

SDA 

C ZONE 

RX1/I1.6 

I1.6 

RX1 

I1.1 

RX1 

TX1/I1.5 

I1.5 

TX1 

I1.0 

TX1 

B ZONE 

Pin 3/I0.6 

I0.6 

Pin 3 

I0.1 

Pin 3 

Pin 2/I0.5 

I0.5 

Pin 2 

I0.0 

Pin 2 

uSD & RS-485 

D53(SD) 

Q2.0 

SD 

SD 

FD RS-485 HD 

HD 

FD 

HD 

FD 

Содержание M-DUINO PLC ARDUINO ETHERNET 58

Страница 1: ...M DUINO PLC ARDUINO ETHERNET 58 I Os ANALOG DIGITAL PLUS PLC ARDUINO ETHERNET 58 I Os ANALOG DIGITAL PLUS...

Страница 2: ...Ref IS MDUINO 58 Rev 0 30 08 2019 1...

Страница 3: ...Ref IS MDUINO 58 Rev 0 30 08 2019 2 Ethernet PLC MDuino 58 PLUS User Guide Revised August 2019...

Страница 4: ...g the directive may damage the controller Improper use of this product may severely damage the controller Refer to the controller s User Guide regarding wiring considerations Before using this product...

Страница 5: ...ce doit tre effectu e par personnel qualifi familiaris avec la fabrication le fonctionnement et les dangers li s au contr leur La maintenance doit tre effectu e avec l quipement hors service et d conn...

Страница 6: ...any codes regulations or standards that apply to the combination of products in the customer s application or use of the product The following are some examples of applications for which particular a...

Страница 7: ...ze risks resulting from the handling or manipulation of such products systems and to avoid possible hazards Disclaimers Weights and Dimensions Dimensions and weights are nominal and they are not used...

Страница 8: ...s during commissioning operation maintenance and repairs caused by for example Hardware defects and or software errors in the sensors controllers actuators and connection technology Response times of...

Страница 9: ...ED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE INDUSTRIAL SHIELDS DISCLAIMS ALL OTHER WARRANTIES EXPRESS OR IMPLIED Limitations of Liability INDUSTRIAL SHIELDS SHALL NO...

Страница 10: ...ecautions 18 3 3 1 Arduino Board 18 3 2 Intended Audience 18 3 3 General Precautions 18 Software interface 18 4 How to connect PLC Arduino to PC 21 5 How to connect PLC to power supply 23 6 M Duino 58...

Страница 11: ...ernet 35 10 7 RTC 36 10 8 uSD 36 Instructions for interconnection between Industrial Shields controllers 38 11 11 1 RS 232 Communication 38 11 2 RS 485 Communication 38 11 2 2 Full Duplex 38 11 3 Ethe...

Страница 12: ...and D the shield from above Having a B and a C in the middle of them The inputs in the zone B are named I0 X being X any number suitable in the Shield Outputs are named as Q0 X and relays as R0 X The...

Страница 13: ...Shield 13 Inputs 13 Digital inputs 6 of which can work as Analog Input 8 Outputs 8 Digital Outputs 3 of which can work as Analog Output 13 Inputs 13 Digital inputs 6 of which can work as Analog Input...

Страница 14: ...58 Rev 0 30 08 2019 13 1 3 A Zone Features Shield A Zone Communication Shield 1x Ethernet 1x USB 1x I2C 3x TTL 1x RS 232 1x HALF FULL Duplex RS 485 1x SPI external Port 1x RTC 1x uSD Socket 1 4 Mechan...

Страница 15: ...a project Cannot be working in a final application An Dig Input 10bit 0 10Vcc 0 to 10Vac Input Impedance 39K Separated PCB ground Rated Voltage 10Vac 7 to 24Vdc I min 2 to 12 mA Galvanic Isolation Rat...

Страница 16: ...M Isolated Output 8bit 24Vcc 5 to 24Vdc I max 70 mA Galvanic Isolation Diode Protected for Relay Rated Voltage 24Vdc Expandability I2C 127 elements Serial Port RS232 RS485 By using this type of signal...

Страница 17: ...terminal Shock resistance 80m s2 in the X Y and Z direction 2 times each Ambient temperature operating 0 to 60 C Ambient humidity operating 10 to 90 no condensation Ambient environment operating With...

Страница 18: ...on equipment 5130 Pulse General To identify the control by which a pulse is started IEC 60417 Graphical symbols for use on equipment 5017 Earth Ground To identify an earth ground terminal in cases wh...

Страница 19: ...ve a serious influence on lives and property if used improperly consult your INDUSTRIAL SHIELDS representative Ensure that the rating and performance characteristics of M Duino are sufficient for the...

Страница 20: ...go to File Preferences located in the top left corner 2 In Additional Boards Manager URLs write the following http apps industrialshields com main arduino boards package_industrialshields_index json...

Страница 21: ...IS MDUINO 58 Rev 0 30 08 2019 20 5 Search for industrialshields on the browser 6 Click install selecting the latest version Following these steps you will be able to see now the Industrial Shields Boa...

Страница 22: ...e are some examples of programming in File Examples M Duino Family Furthermore there are some extra libraries that can be found in Industrial Shields github https github com IndustrialShields How to c...

Страница 23: ...Ref IS MDUINO 58 Rev 0 30 08 2019 22 Select the correct M Duino Board M Duino 58 Select correct port...

Страница 24: ...ories regardless of where use of the device is intended The equipment must be powered from an external power source in accordance with IEC 61010 1 whose output is MBTS and is limited in power accordin...

Страница 25: ...3 50 51 52 Reset Vin5 2 I2C SS I2C SS RX0 SS TX0 SS RX1 SS TX1 SS RX2 serial 2 TX2 serial 2 RS485 RS485 RS485 RS485 Arduino Pin SPI SPI SPI SPI 5V Arduino Pin Gnd Gnd Power Supply Base common unit A...

Страница 26: ...t Arduino mega has auto reset when using serial communication code Set switch to OFF when using serial communication When uploading code to Arduino Mega set switch to ON Ethernet Arduino Power Connect...

Страница 27: ...put GND I0 3 Digital Input GND I0 2 Digital Input GND I0 1 Digital Input GND I0 0 Digital Input B Zone M Duino Connector Arduino Pin Function GND A0 7 1 A0 6 1 A0 5 1 Q Vdc COM Q0 7 1 Q0 6 1 Q0 5 1 Q0...

Страница 28: ...put GND I1 3 Digital Input GND I1 2 Digital Input GND I1 1 Digital Input GND I1 0 Digital Input C Zone M Duino Connector Arduino Pin Function GND A1 7 1 A1 6 1 A1 5 1 Q Vdc COM Q1 7 1 Q1 6 1 Q1 5 1 Q1...

Страница 29: ...GND I2 3 Digital Input GND I2 2 Digital Input GND I2 1 Digital Input GND I2 0 Digital Input D Zone M Duino Connector Arduino Pin Function GND A2 7 A2 6 1 A2 5 1 Q Vdc COM Q2 7 Q2 6 1 Q2 5 1 Q2 4 Q2 3...

Страница 30: ...Choosing between RX1 or the input I1 6 If this switch is ON it enables the I1 6 input and disables the RX1 If this switch is OFF it enables RX1 and disables I1 6 1 TX1 I1 5 Choosing between TX1 or th...

Страница 31: ...If this switch is ON it enables the Half Duplex HD option and disables the FD If this switch is OFF it enables Full Duplex FD and disables HD 1 RTC SDA This switch enables the communication to communi...

Страница 32: ...hat will provide this digital output is represented with QX X being X any number of the tables above If it is desired to use an Analog Output the pin must be set to OFF and the pin that will provide t...

Страница 33: ...uration means that when the pin is at rest nothing connected to it it always reads a HIGH value In this case it reads 5V when nothing is connected The pull up configuration is stablished by default in...

Страница 34: ...o correctly work with these pins 9 4 SPI MISO MOSI SCK These pins can only work as a 5V pins if the Ethernet protocol is not going to be used As the Ethernet protocol uses the SPI to communicate with...

Страница 35: ...below Function Arduino Pin DI 14 RO 15 RE 11 DE 46 For the RS 485 communication protocol there is only one switch that affects in this communication The RS 485 protocol will be always enabled the only...

Страница 36: ...in3 21 20 1 0 19 18 15 14 2 3 Check the switch configuration at section 8 to enable SS pins 10 5 TTL M Duino has two TTL ports RX0 TX0 RX1 TX1 TTL0 is accessed with the function Serial pins 0 and 1 of...

Страница 37: ...uSD The micro SD uses the SPI communication to interact with the Arduino Mega The SPI protocol is always enabled as there are no switches that configure it However there is a switch that must be place...

Страница 38: ...hine Unexpected operation of a process or machine could result in death or injury to personnel and or property damage Before inserting a memory card always ensure that the CPU is offline and in a safe...

Страница 39: ...f IS MDUINO 58 Rev 0 30 08 2019 38 Instructions for interconnection between Industrial Shields 11 controllers 11 1 RS 232 Communication 11 2 RS 485 Communication 11 2 1 1 Half Duplex 11 2 2 Full Duple...

Страница 40: ...Ref IS MDUINO 58 Rev 0 30 08 2019 39 11 3 Ethernet For an Ethernet communication between Industrial Shields equipment a SFTP CAT 6 Ethernet crossover cable must be used...

Страница 41: ...Ref IS MDUINO 58 Rev 0 30 08 2019 40 I O technical details 12 Digital Output Waveform Digital Out put Turn off PWM Waveform...

Страница 42: ...Ref IS MDUINO 58 Rev 0 30 08 2019 41 Analog Out Turn On Analog Out Turn Off Analog Digital input Turn on...

Страница 43: ...Ref IS MDUINO 58 Rev 0 30 08 2019 42 Typical Connections 13...

Страница 44: ...Ref IS MDUINO 58 Rev 0 30 08 2019 43...

Страница 45: ...Ref IS MDUINO 58 Rev 0 30 08 2019 44...

Страница 46: ...Ref IS MDUINO 58 Rev 0 30 08 2019 45...

Страница 47: ...Ref IS MDUINO 58 Rev 0 30 08 2019 46...

Страница 48: ...406 connector from Phoenix contact FK MC 0 5 10 ST 2 5 Connection details Article reference MC 0 5 10 G 2 5 THT Height 8 1mm Pitch 2 5mm Dimension 22 5mm Pin dimensions 0 8x0 8mm Pin spacing 2 50mm Ar...

Страница 49: ...chanical Characteristics 15 Dimension M Duino 58 I Os PLUS DIN Rail mounting For optimal operation of the product it must be located in an electrical cabinet with IK08 mechanical protection The minimu...

Страница 50: ...witches and contactors in a dedicated electric cabinet and keep the cabinet ventilated If the location has high ambient temperature or heat generating equipment nearby install forced convection device...

Страница 51: ...ese systems The means employed for grounding or insulating the equipment from ground should be checked to assure its integrity Accumulations of dust and dirt on all parts including on semiconductor he...

Страница 52: ...ning can damage the screws and or the module with the risk of falling short circuits and malfunctions Before handling a module dispose of the electrostatic charge accumulated by the human body by touc...

Страница 53: ...Ref IS MDUINO 58 Rev 0 30 08 2019 52 Revision Table 17 Revision Number Date Changes 0 30 08 2019 First implementation...

Страница 54: ...08 2019 53 About Industrial Shields Direction F brica del Pont 1 11 Zip Postal Code 08272 City Sant Fruit s de Bages Barcelona Country Spain Telephone 34 938 760 191 34 635 693 611 Mail industrialshie...

Отзывы: