Indunium 2i User Guide
31 / 77
whether it is ON or OFF
Event Counter: under event counter mode
Null: DI disabled
Filtering
Software filtering is used to control switch bounces.
Input from 0 to 10000ms.
0
Count Trigger
Available when DI under Event Counter mode.
Input from 0 to 30000. (0=will not trigger alarm)
It will trigger alarm when counter reaching this figure. After
triggering alarm, DI keeps counting but will not trigger alarm
again.
To clear the counter, use SMS command or Modbus polling
command.
SMS command: please refer to 5.3 SMS Commands for Remote
Control->Clear Event Counter
Modbus address: please refer to 5.4 Modbus Address Mapping
0
Counter Active
Available when DI under Event Counter mode.
In Event Counter mode, the channel accepts limit or proximity
switches and counts events according to the ON/OFF status.
When “Lo to Hi” is selected, the counter value increases when
the attached switch is pushed. When “Hi to Lo” is selected, the
counter value increases when the switch is pushed and
released.
Lo to Hi
Counter
Start
When Power On
Available when DI under Event Counter mode.
Start counting as soon as power on the modem when enable
this option.
If “Counter Start When Power On” is disabled, it will also start
counting when receiving SMS command or Modbus polling
command.
SMS command: please refer to 5.3 SMS Commands for Remote
Control->Start Event Counter
Modbus address: please refer to 5.4 Modbus Address Mapping
Disable
Triggering Alarm
The SMS to receive upon triggering alarm. (70 ASIC II char max) Null
Recovering Alarm
The SMS to receive upon recovering alarm. (70 ASIC II char
max)
Null
Phone Group
The alarm SMS will send to specified phone group.
Each phone group include up to 10 phone numbers.
Null
Note: the Event Counter value will be reset to zero if power is disconnected.