4.
Route the connecting cable correctly through the cable gland. Make especially certain that the cable gland
is suitable for the dimensions of the type of cable that will be connected. This is necessary to ensure the IP
protection.
5.
Cut the cable to length.
6.
Connect the cable to the terminals. The standard terminals in the junction box are suitable as standard for
a core diameter of 0-4 mm².
7.
Check the connections that have been made.
8.
Close the junction box.
WARNING
The installation must be carried out in accordance with (NEN-EN) IEC 60079-14.
6.3
Connections
In the light fitting junction box there is a terminal block as shown in the illustration.
The following connection can be made:
L-N
: Permanent connection for the power supply.
In case of a flying lead, the free end of the permanently connected unterminated power cable shall be
connected by using a suitable certified junction box. For use in the presence of combustible dust, the junction
box shall have a degree of protection IP6X according to EN 60529.
The neutral (code N – blue), the phase (code L – brown) and earth (code PE, yellow-green) need to be
connected.
7.
Use
7.1
Commissioning
The light fitting can be switched on immediately after installation.
7.2
Insulation test
Installations in which IQL®-FL light fittings are installed can be checked with an insulation test. For this test,
apply a maximum of 500 VDC between earth and a phase
or
neutral connection.
WARNING
Never apply more than 500 VDC between a phase and a neutral connection.
During production, all light fittings have been subjected to a dielectric test (1500 VAC for 60 seconds). In
addition, the light fittings have also been subjected to an endurance test.
8.
Maintenance
The light fitting is ‘sealed for life’ and cannot be opened. Consequently maintenance as laid down in the IEC
60079-17 standard is not applicable; a visual inspection for correct operation will suffice.