4.

 

Route the connecting cable correctly through the cable gland. Make especially certain that the cable gland 

is suitable for the dimensions of the type of cable that will be connected. This is necessary to ensure the IP 

protection. 

5.

 

Cut the cable to length.

 

6.

 

Connect the cable to the terminals. The standard terminals in the junction box are suitable as standard for 

a core diameter of 0-4 mm².

 

7.

 

Check the connections that have been made.

 

8.

 

Close the junction box. 

 

 

 

WARNING 

The installation must be carried out in accordance with (NEN-EN) IEC 60079-14.

 

 

6.3

 

Connections 

In the light fitting junction box there is a terminal block as shown in the illustration. 

 

 
 

The following connection can be made: 

L-N 

: Permanent connection for the power supply. 

 

In case of a flying lead, the free end of the permanently connected unterminated power cable shall be 

connected by using a suitable certified junction box. For use in the presence of combustible dust, the junction 

box shall have a degree of protection IP6X according to EN 60529. 

The neutral (code N – blue), the phase (code L – brown) and earth (code PE, yellow-green) need to be 

connected. 

 

7.

 

Use  

 

7.1

 

Commissioning 

The light fitting can be switched on immediately after installation.  

 

7.2

 

Insulation test 

Installations in which IQL®-FL light fittings are installed can be checked with an insulation test. For this test, 

apply a maximum of 500 VDC between earth and a phase 

or

 neutral connection. 

 

 

WARNING 

Never apply more than 500 VDC between a phase and a neutral connection.

 

During production, all light fittings have been subjected to a dielectric test (1500 VAC for 60 seconds). In 

addition, the light fittings have also been subjected to an endurance test. 

 

 

8.

 

Maintenance 

The light fitting is ‘sealed for life’ and cannot be opened. Consequently maintenance as laid down in the IEC 

60079-17 standard is not applicable; a visual inspection for correct operation will suffice. 

Содержание IQL Albireo Floodlight

Страница 1: ...IQL Albireo Floodlight User Manual...

Страница 2: ...ons 6 5 1 General 6 5 2 Dimensions 7 6 Installation 8 6 1 Preparation 8 6 2 Assembly 8 6 3 Connections 9 7 Use 9 7 1 Commissioning 9 7 2 Insulation test 9 8 Maintenance 9 9 Recycling 10 10 Contact det...

Страница 3: ...n box Never open the light fitting housing Do not clean the light fitting with a high pressure steam or water jet This will avoid damage that falls outside the guarantee terms 2 Warranty 2 1 General T...

Страница 4: ...Low temperature range IQL55 FL LT IQL85 FL LT IQL165 FL LT Normal temperature range IQL55 FL IQL85 FL IQL165 FL 2 Ambient temp Low temperature range 40 C up to 40 C Normal temperature range 20 C up to...

Страница 5: ...ormal temperature range IQL55 FL IQL85 FL IQL165 FL 2 Ambient temp Low temperature range 40 C up to 40 C Normal temperature range 20 C up to 40 C 3 Serial number 4 Year of Manufacture 5 Frequency AC 5...

Страница 6: ...ure voedingsmiddelenindustriefood industry 5 Specifications 5 1 General Housing corrosion resistant aluminium with a polyurethane varnish RAL7032 gray Lens toughened glass Colour recognition Ra 80 Ing...

Страница 7: ...User Manual IQL Albireo Floodlight User Manual IQL Albireo Floodlight 7 Version 5 1 201302 5 2 Dimensions 5 2 1 IQL 55 FL and IQL 85 FL 5 2 2 IQL 165 FL...

Страница 8: ...W 165 W 100 120 VAC DC 200 277 VAC DC 100 120 VAC DC 200 277 VAC DC 200 277 VAC DC Inrush currents 16 12 16 12 24 Peak duration 170 s 170 s 170 s 170 s 140 s When using 30 mA earth leakage switches p...

Страница 9: ...ected unterminated power cable shall be connected by using a suitable certified junction box For use in the presence of combustible dust the junction box shall have a degree of protection IP6X accordi...

Страница 10: ...s within the context of the WEEE directive Contact your local partner see the chapter Contact details The local partner will be responsible for further processing 10 Contact details IMT B V Pascalweg...

Страница 11: ...ollowing standards and or technically related specifications are met Standard Issue Title EN 60079 0 2009 Electrical apparatus for potentially explosive atmospheres General requirements EN 60079 7 200...

Страница 12: ...IMT B V Pascalweg 10a 4104 BG Culemborg P O Box 88 4100 AB Culemborg Tel 31 0 88 12 69 100 Fax 31 0 88 12 69 101 www imt eu sales imt eu...

Отзывы: