6.

 

Installation 

 

6.1

 

Preparation 

1.

 

Check that the light fitting will be installed in an environment that matches the ambient 

 

temperatures, gas group and temperature class. This data is shown on the light fitting type plate.  

 

 

WARNING 

The installation of the light fitting in an environment that does not match the specified 

conditions can result in a dangerous situation. 

 

 

WARNING 

The installation of the light fitting in an environment that does not match the specified 

ambient temperatures can have a strong negative effect on the life span of the light 
fitting. 

 

2.

 

Choose the correct type of protection for the light fitting. The protection device needs to  

 

be a fuse or a circuit breaker of at least 4 kA with a C characteristic.  

3.

 

Determine the number of light fittings that can be installed in each group. Consult the following table for  

 

this. 

 

 

Installation 

protection 

55 W 

85 W 

165 W 

100-120 

VAC/DC 

200-277 

VAC/DC 

100-120 

VAC/DC 

200-277 

VAC/DC 

200-277 

VAC/DC 

B Type, 10 A 

15 

20 

15 

20 

10 

C type, 10 A 

15 

20 

15 

20 

10 

B Type, 16 A 

22 

30 

22 

30 

16 

C type, 16 A 

26 

35 

26 

35 

16 

 
 

55 W 

85 W 

165 W 

100-120 

VAC/DC 

200-277 

VAC/DC 

100-120 

VAC/DC 

200-277 

VAC/DC 

200-277 

VAC/DC 

Inrush currents 

16 

12 

16 

12 

24 

Peak duration 

170 μs 

170 μs 

170 μs 

170 μs 

140 μs 

 

When using 30 mA earth leakage switches, provision must be made for a maximum of 30 light fittings on one 

switch. 

 

6.2

 

Assembly

 

1.

 

Take the light fitting out of the packaging. 

2.

 

Inspect the light fitting for mechanical damage. 

 

 

WARNING 

The installation of the light fitting in an environment that does not match the specified 

conditions can result in a dangerous situation.

 

 

 

WARNING 

The installation of the light fitting in an environment that does not match the specified 

ambient temperatures can have a strong negative effect on the life span of the light 

fitting.

 

 

3.

 

Mount the light fitting. 

 

Ensure there is a reliable connection to the earthing system, both with the external earthing point and 

with the connection in the light fitting junction box. 

 

Ensure that the cable gland is suitable for the dimensions of the type of cable that will be connected 

and has an IP level of IP66, IP67 or IP68 in conformance with EN 60529, and in case of an explosion 

proof lighting fixture, is Ex-e certified according to IEC 60079-7. This is necessary to ensure the IP 

protection, and to be suitable for a hazardous environment. 

 

 

 

WARNING 

Ensure that there is no mechanical load applied to the light fitting during installation.  

 

Содержание IQL Albireo Floodlight

Страница 1: ...IQL Albireo Floodlight User Manual...

Страница 2: ...ons 6 5 1 General 6 5 2 Dimensions 7 6 Installation 8 6 1 Preparation 8 6 2 Assembly 8 6 3 Connections 9 7 Use 9 7 1 Commissioning 9 7 2 Insulation test 9 8 Maintenance 9 9 Recycling 10 10 Contact det...

Страница 3: ...n box Never open the light fitting housing Do not clean the light fitting with a high pressure steam or water jet This will avoid damage that falls outside the guarantee terms 2 Warranty 2 1 General T...

Страница 4: ...Low temperature range IQL55 FL LT IQL85 FL LT IQL165 FL LT Normal temperature range IQL55 FL IQL85 FL IQL165 FL 2 Ambient temp Low temperature range 40 C up to 40 C Normal temperature range 20 C up to...

Страница 5: ...ormal temperature range IQL55 FL IQL85 FL IQL165 FL 2 Ambient temp Low temperature range 40 C up to 40 C Normal temperature range 20 C up to 40 C 3 Serial number 4 Year of Manufacture 5 Frequency AC 5...

Страница 6: ...ure voedingsmiddelenindustriefood industry 5 Specifications 5 1 General Housing corrosion resistant aluminium with a polyurethane varnish RAL7032 gray Lens toughened glass Colour recognition Ra 80 Ing...

Страница 7: ...User Manual IQL Albireo Floodlight User Manual IQL Albireo Floodlight 7 Version 5 1 201302 5 2 Dimensions 5 2 1 IQL 55 FL and IQL 85 FL 5 2 2 IQL 165 FL...

Страница 8: ...W 165 W 100 120 VAC DC 200 277 VAC DC 100 120 VAC DC 200 277 VAC DC 200 277 VAC DC Inrush currents 16 12 16 12 24 Peak duration 170 s 170 s 170 s 170 s 140 s When using 30 mA earth leakage switches p...

Страница 9: ...ected unterminated power cable shall be connected by using a suitable certified junction box For use in the presence of combustible dust the junction box shall have a degree of protection IP6X accordi...

Страница 10: ...s within the context of the WEEE directive Contact your local partner see the chapter Contact details The local partner will be responsible for further processing 10 Contact details IMT B V Pascalweg...

Страница 11: ...ollowing standards and or technically related specifications are met Standard Issue Title EN 60079 0 2009 Electrical apparatus for potentially explosive atmospheres General requirements EN 60079 7 200...

Страница 12: ...IMT B V Pascalweg 10a 4104 BG Culemborg P O Box 88 4100 AB Culemborg Tel 31 0 88 12 69 100 Fax 31 0 88 12 69 101 www imt eu sales imt eu...

Отзывы: