For example, if the three measured voltages were 442, 460, and
454 volts, the average would be:

(442 + 460 + 454) / 3 = 452

The percentage of imbalance is then:

(452 – 442) x 100 / 452 = 2.2 %

This exceeds the maximum allowable of 2%.

A terminal block is provided for main power connection to the
main power source.  The main power source should be 
connected to the terminal block through an appropriate 
disconnect switch.  A separate lug for grounding the unit is also
provided in the main control panel.  Electrical phase sequence
must be checked at installation and prior to start-up.  Operation
of the compressor with incorrect electrical phase sequencing
will result in mechanical damage to the compressors.  The
phasing must be checked with a phase sequence meter prior to
applying power. The proper sequence should read “ABC” on the
meter. If the meter reads “CBA”, open the main power 
disconnect switch and switch two line leads on the line power
terminal blocks (or the unit mounted disconnect). All 
components requiring electric power are wired in-phase at the
factory.  Do not interchange any load leads that are from the

unit contactors or the motor terminals.

WARNING: It is imperative that L1-L2-L3 are 
connected in the A-B-C phase sequence to 
prevent equipment damage due to reverse 
rotation.

WARNING: The control panel and safeties are 
wired such that connecting the appropriate 
power source to the main terminal block 
energizes the entire electric circuitry of the 
unit.  A control transformer has been factory 
wired to step down the incoming power to the 
115-volt control power.  Electric power at the 
main disconnect should be shut off before 
opening access panels for repair or 
maintenance. The unit must be properly 
grounded in compliance with local and national 
codes.

Process Connections 

The importance of properly sized piping or hose between the
temperature control unit and the process equipment cannot be
overemphasized. In general, run full size piping out to the
process and then reduce the pipe size to match the connections
on the process equipment. One of the most common causes of
poor temperature control unit performance is poorly designed
piping. Avoid unnecessarily long lengths of hoses and piping as

well as quick disconnect fittings that offer high resistance to
water flow.  When manifolds are required for water distribution,
they should be installed as close to the point of use as possible. 

The return line should be the same size as the supply line. In
addition to the process water connections, the unit requires a
cooling water supply and return connection. We recommend
shut-off valves at each machine to allow for isolation and
removal of the unit.

START-UP  

Every unit is factory set to deliver temperature controlled water
in accordance with the standard operating specifications for that
particular unit.  Due to variables involved with different 
applications and different installations, minor adjustments may
be required during the initial start-up to ensure proper operation.
The following start-up procedure should be followed in
sequence. If trouble is encountered during start-up, the fault can
usually be traced to one of the control or safety devices. This
outline can be used as a checklist for the initial start-up and for
subsequent start-ups if the unit is taken out of service for a 
prolonged period of time.

1.

Assure the main power source is connected properly, that it
matches the voltage shown on the nameplate of the unit,
and that it is within the voltage utilization range given in
Table 1. Electrical phase sequence must be checked at
installation and prior to start-up. Operation of the unit with
incorrect electrical phase sequencing will result in improper
performance and potential damage. The phasing must be
checked with a phase sequence meter prior to applying
power. The proper sequence should read “ABC” on the
meter. If the meter reads “CBA”, open the main power dis-
connect switch and switch two line leads on the line power
terminal blocks (or the unit mounted disconnect). All com-
ponents requiring electric power are wired in-phase at the
factory.  Do not interchange any load leads that are from
the unit contactors or the motor terminals.

WARNING: It is imperative that L1-L2-L3 are 
connected in the A-B-C phase sequence to 
prevent equipment damage due to reverse 
rotation.

2.

Once proper power connection and grounding have been
confirmed, turn the main power on.

3.

Check all water line connections to ensure they are properly
sized and installed. All water lines and connectors should
be rated for a minimum of 250°F (121°C) and 150 PSI (10.5
Bar). We recommend the cooling water supply and return
lines are of metal composition (black steel, galvanized or
copper).

Содержание Hydra Pressurized

Страница 1: ...Company Hydra Pressurized Open Loop Mold Temperature Controllers INSTRUCTION MANUAL January 2007 IMS Company 10373 Stafford Road Chagrin Falls OH 44023 5296 Telephone 440 543 1615 Fax 440 543 1069 Email sales imscompany com Website www imscompany com Hydra is a trademark of IMS Company ...

Страница 2: ... 8 Purge 8 Alarm Silence 8 Lower Set Point Temperature 8 Raise Set Point Temperature 8 Low Pressure 8 High Temp Safety 8 Pump Motor Overload 8 Over Set Point 9 Under Set Point 9 Pump On 9 Heat 9 Cool 9 Vent 9 Probe Fault 9 Changing Temperature Display Scale 9 Seal Saver 10 Auto Tune 10 Diagnostic Error Codes 11 Table 3 Diagnostic Error Codes 11 CONTROL OPTIONS 12 Return Water Temperature Display 1...

Страница 3: ...r Modulating Valve 13 Pressure Switch 13 Pressure Relief Valve 14 STANDARD OPTIONS 14 Stacking Bracket Kit RA RB series 14 Mold Water Purge 14 Crash Cool 14 PREVENTIVE MAINTENANCE 14 Once a Week 15 Once a Month 15 TROUBLESHOOTING 16 CHARTS PUMP CURVES 17 Table 5 Single Zone Unit Electrical Specifications 17 Table 6 Dual Zone Unit Electrical Specifications 18 Figure 1 RA RAD RB RBD Series Pump Curv...

Страница 4: ...ing Inspection Each unit is skid mounted and boxed or crated to protect it during shipping Before accepting delivery check the box or crate for visible damage If damage is evident it should be properly documented on the delivery receipt and the box or crate should be immediately removed to allow for detailed inspection of the unit Check for broken water lines damaged controls or any other major co...

Страница 5: ...s well as quick disconnect fittings that offer high resistance to water flow When manifolds are required for water distribution they should be installed as close to the point of use as possible The return line should be the same size as the supply line In addition to the process water connections the unit requires a cooling water supply and return connection We recommend shut off valves at each ma...

Страница 6: ...5 PSI 1 75 Bar and 50 PSI 3 5 Bar If the supply cooling water pressure is higher than 50 PSI 3 5 Bar a pressure regulating valve should be installed on the supply line to the temperature control unit For assistance in installing a pressure regulating valve please contact our Tech Service Department 6 Turn on the control power by pressing the Power button located on the control panel of the unit Th...

Страница 7: ...ol Fault Logic Alarm Manual Remote Fault Alarm Pump Shut Heater Shut Unit Shut Reset Reset Alarm Indication Off Off Off Required 1 Required 2 Activated 3 Low Pressure LED Yes Yes Yes No No Yes High Temperature Safety LED Yes Yes Yes Yes No Yes Pump Motor Overload LED Yes Yes Yes Yes Yes Yes Over Set Point LED No No No No No Yes Under Set Point LED No No No No No Yes Probe Fault LED Yes Yes Yes Yes...

Страница 8: ...epressing the Alarm Silence button will open the contact that was closed when the alarm occurred The contact will not close again until the alarm has been reset and a subsequent alarm has been triggered Lower Set Point Temperature Depressing and then releasing the Lower Set Point Temperature button will decrease the set point temperature by 1 F or 1 C If the Lower Set Point Temperature button is h...

Страница 9: ...ted while the microprocessor is performing an Auto Vent sequence This sequence is performed each time the Start button is pressed to energize the unit unless the temperature is above 150 F The Auto Vent sequence opens the cooling solenoid or modulating valve for 30 seconds to vent air from the mold circuit Then the valve is kept open and the pump is energized for an additional 30 seconds The Vent ...

Страница 10: ...re a particular application may require additional fine tuning of the control parameters To make this procedure as simple as possible this controller has been equipped with an Auto Tune function The Auto Tune function is designed to automatically select the best control parameters based upon the particular system that the unit is connected to At the factory certain parameters have been limited so ...

Страница 11: ...tact Manufacturer for repair or replacement configuration change or invalid 111 Fixed parameter associated Controller requires servicing Contact Manufacturer for repair or replacement with range invalid 112 Setpoint out of temperature range Controller requires servicing Contact Manufacturer for repair or replacement 113 RAM hardware failure Controller requires servicing Contact Manufacturer for re...

Страница 12: ...connect the controller and the unit All control functions are available to the operator at the location of the remote panel and no control functions are available at the location of the unit SPI Communications This option provides an RS 485 communication port located below the control panel on the front of the unit The serial communications will be multi drop half duplex SPI 3 01 compatible and wi...

Страница 13: ...st not be defeated A small pump seal flush line is provided to continuously flush the pump seal of dirt and debris Construction Pump Assembly The centrifugal close coupled pump features a specially designed cast volute to eliminate fittings and provide easy connection to the heater and or mixing tubes The pump volute is constructed of cast iron The through 2 HP pumps have stainless steel impellers...

Страница 14: ...ss the Stop button This leaves the unit on but puts the microprocessor in an inactive mode The Power button light should still be illuminated 2 Close the valve on the Cooling Water In line to shut off the supply of water 3 Connect the compressed air supply to the ball valve on the back of the unit 4 Open the ball valve to let the compressed air into the mold circuit 5 Press the Purge button on the...

Страница 15: ...ay from the normal operating pressure 3 Check the pump for leaks in the seal area Replace pump seal if necessary Repeat items 1 through 3 listed above and continue with the following Once a Month 4 With the main disconnect shut off check the condition of electrical connections at all contactors starters and con trols Check for loose or frayed wires 5 Check the incoming voltage to make sure it is w...

Страница 16: ...ctioning correctly and replace any defective components Microprocessor controller failure Replace controller Failure of thermocouple Replace thermocouple Failure of heater Replace heater Failure of heater contactor Replace heater contactor Unable to cool properly Cooling water supply is not Check to make sure the cooling water supply is of sufficient sufficient temperature volume and pressure for ...

Страница 17: ...20 2 9 24 9 22 6 11 3 9 0 1 2 6 6 6 0 3 0 2 4 69 4 63 0 31 8 25 4 RA183A 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA183B 2 9 24 9 22 6 11 3 9 0 1 3 9 9 9 0 4 5 3 6 72 7 66 0 33 3 26 6 RA1850 2 9 24 9 22 6 11 3 9 0 1 5 16 5 15 0 7 5 6 0 79 3 72 0 36 3 29 0 RA1875 2 9 24 9 22 6 11 3 9 0 1 7 5 24 2 22 0 11 0 8 8 87 0 79 0 39 8 31 8 RA2408 2 9 24 9 22 6 11 3 9 0 1 0 75 3 7 3 4 1 ...

Страница 18: ...1810 4 9 24 9 22 6 11 3 9 0 2 1 3 7 3 4 1 7 1 4 132 4 120 3 60 4 48 3 RAD1820 4 9 24 9 22 6 11 3 9 0 2 2 6 6 6 0 3 0 2 4 138 2 125 5 63 0 50 3 RAD183A 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD183B 4 9 24 9 22 6 11 3 9 0 2 3 9 9 9 0 4 5 3 6 144 8 131 5 66 0 52 7 RAD1850 4 9 24 9 22 6 11 3 9 0 2 5 16 5 15 0 7 5 6 0 158 0 143 5 72 0 57 5 RAD1875 4 9 24 9 22 6 11 3 9 0 2 7 5...

Страница 19: ...e prepared a custom set of drawings for your unit and placed them inside the control panel prior to shipment Please refer to these drawings when troubleshooting servicing and installing the unit If you cannot find these drawings or wish to have additional copies please contact our Tech Service Department and reference the serial number of your unit ...

Страница 20: ... the equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or which has been altered and or repaired without express factory authorization If equipment is installed in hostile environments unless such conditions were specified at the time of purchase or the serial number has been removed or defaced this warranty shall not appl...

Отзывы: