What Results Are Generally Acceptable
Atmospheric Gas Fired Burners
•
Oxygen
....................................................................................... 7 to 9% O2
•
Stack Temperature
................................................................... 325 to 500°F
•
Draft
(Water Column Inches) .................................................... -.02 to -.04wc”
•
Carbon Monoxide
(parts per million) ...................................... <100ppm
Gas Fired Power Burners
•
Oxygen
....................................................................................... 3 to 6% O2
•
Stack Temperature
................................................................... 275 to 500°F
•
Stack Draft
(Water Column Inches).......................................... -.02 to -.04wc”
•
Overfire Draft
(Water Column Inches)..................................... -.02wc”
•
Carbon Monoxide
(parts per million) ...................................... <100ppm
Oil Fired Burners (#2 Oil Fuel)
•
Oxygen
....................................................................................... 4 to 7% O2
•
Stack Temperature
................................................................... 325 to 600°F
•
Stack Draft
(Water Column Inches).......................................... -.04 to -.06wc”
•
Overfire Draft
(Water Column Inches)..................................... -.02wc”
•
Carbon Monoxide
(parts per million) ...................................... <100ppm
•
Smoke
........................................................................................ 0 (or manufacturer’s recommendation)
Positive Overfire Gas & Oil
•
Oxygen
....................................................................................... 3 to 9% O2
•
Stack Draft
(Water Column Inches).......................................... -.02 to -.04wc”
•
Overfire Draft
(Water Column Inches)..................................... +0.4 to +0.6wc”
•
Carbon Monoxide
(parts per million) ...................................... <100ppm
NOTE: Follow manufacturer guidelines for the specific equipment being serviced.
Typical Excess Air Level
O2% (measured) Excess Air %
Natural gas 3% 16.7%
Light Oil 5% 31%
Coal 8% 62%