Keep pressed the
key until “SP “ is displayed ( then release the key). The display shows
the set point value and the
symbol blinking.
Use the
keys to increase or decrease the value.
To confirm press the
key or wait 10”sec.
2.2.6 Operating mode
2.2.6.1 Cooling
Press
key to choose the cooling mode desired:
(manual),
(automatic),
the machine starts cooling function.
If the probe detects, inside the building, a humidity value 5% more than the value setted, the ma-
chine goes in ventilation mode (cooling stand
-
by) If the probe detects, inside the building, a humidi-
ty value less than value setted, the machine goes back in cooling mode.
It’s possible to set the air flow by choosing the fan speed by using the key
It’s also possible to set automatic speed function FA (see next par).
To guarantee pads longer life, the evaporative cooler has the tank’s water changes every 4 hours
(factory default) and a pads self cleaning cycle when the machine is switched off:
2.2.5.7 Locking/Unlocking remote control unit
It is possible to lock the remote control unit to avoid the control by anyone.
To lock the remote command unit the
HL
parameter value must be modified from NO to YES.
Modify the HL parameter as follows:
•
Keep pressed together the
keys more than 2”sec until the display shows PA.
•
Press the
key twice.
•
Press the
or
keys to find the parameter to be changed. In this case choose HL.
•
Press the
key to see the current setted value.
•
Press the
or
keys to change the value.
•
Press the
key again to go back.
To save the modification and exit press the
key or wait 30”sec.
When the remote control is locked, display shows Loc when pressing every key. To temporary
unlock the remote control, keep the key
pressed until the display shows oFF. The remote
control goes automatically back to locked status after 15”sec. from last key pressing.