11 Electromagnetic

compatibility (EMC)

11-1 General

In accordance with the provisions described in
the European Commission Guidelines
Document on Council Directive 89/336/EEC,
IMO has chosen to classify the Jaguar VXM
range of Inverters as “Complex Components.

Classification as a “Complex Components”
allows a product to be treated as an
“apparatus”, and thus permits compliance with
the essential requirements of the EMC Directive
to be demonstrated to both an integrator of
Jaguar Inverters and to his customer or the
installer and the user.

Jaguar Inverters are supplied ‘CE-marked’,
signifying compliance with EC Directive
89/336/EEC when fitted with specified filter units
installed and earthed in accordance with this
sheet.

This Specification requires the following
performance criteria to be met.

EMC product standard EN61800-3:1997
+A11:2000

Immunity: Second environment (Industrial

environment) 

Emission: See tables 1 and 2

11-2 Recommended

Installation Instructions

It is necessary that to conform to EMC Directive,
these instructions must be followed.

Follow the usual safely procedures when
working with electrical equipment. All electrical
connections to the filter, Inverter and motor must
be made by a qualified electrical technician.

1) Use the correct filter according to Table

11-1.

2) Install the Inverter and filter in the electrically
shielded metal wiring cabinet.

3) The back panel of the wiring cabinet of board
should be prepared for the mounting
dimensions of the filter. Care should be taken to
remove any paint etc. from the mounting holes
and face area of the panel. This will ensure the
best possible earthing of the filter.

4) Use the screened cable for the control, motor
and other main wiring which are connected to
the Inverter, and these screens should be
securely earthed.

5) It is important that all wire lengths are kept as
short as possible and that incoming mains and
outgoing motor cables are kept well separated.

To minimize the conducted radio disturbance in
the power distribution system, the length of the
motor cable should be as short as possible.

Finally, it is the customer’s responsibility to
check whether the equipment conforms to
EMC directive.

11 Electromagnetic compatibility (EMC)

11-1

First environment

UNRESTRICTED

RESTRICTED

VXM 40 to VXM 1500

when . . .

Fitted with ‘RFM’ type
EMC filter and
installed as shown in
Fig. 11-5

+

10m screened motor
cable maximum

+

Carrier freq. 

 8kHz

+

No option cards or bus
modules fitted

With no option cards or fieldbus
modules fitted

VXM1850 and higher ratings

With option cards or fieldbus modules
fitted

All VXM models

WARNING

This is a product of the restricted
sales distribution class according to
IEC 61800-3.

In a domestic environment this
product may cause radio interference
in which case the user may be
required to take adequate measures.

Table 1

Second environment

100A

100A

VXM 40 to VXM 2200

when . . .

Fitted with ‘2E’ type EMC filter
and installed as shown in Fig.
11-5 (page 11-4 VXM main
instruction manual

+

10m screened motor cable
maximum

+

Carrier freq. 

 4kHz

VXM 30K or larger

when . . .

10m screened motor cable
maximum

+

Carrier freq. 

 4kHz

Table 2

11

157

Содержание Jaguar VXM

Страница 1: ...Instruction manual IMO Jaguar VXM General Purpose Inverter Three phase 400V 0 4 400kW...

Страница 2: ......

Страница 3: ...12 1...

Страница 4: ......

Страница 5: ...1...

Страница 6: ...2...

Страница 7: ...3...

Страница 8: ...4...

Страница 9: ...5...

Страница 10: ...6...

Страница 11: ...7...

Страница 12: ...8...

Страница 13: ...9...

Страница 14: ...10...

Страница 15: ...11...

Страница 16: ...12...

Страница 17: ...13...

Страница 18: ...14...

Страница 19: ...15...

Страница 20: ...16...

Страница 21: ...17...

Страница 22: ...18...

Страница 23: ...19...

Страница 24: ...20...

Страница 25: ...21...

Страница 26: ...22...

Страница 27: ...23...

Страница 28: ...24...

Страница 29: ...25...

Страница 30: ...26...

Страница 31: ...27...

Страница 32: ...28...

Страница 33: ...29...

Страница 34: ...30...

Страница 35: ...31...

Страница 36: ...32...

Страница 37: ...33...

Страница 38: ...34...

Страница 39: ...35...

Страница 40: ...36...

Страница 41: ...37...

Страница 42: ......

Страница 43: ...39...

Страница 44: ...40...

Страница 45: ...41...

Страница 46: ...42...

Страница 47: ...43...

Страница 48: ...44...

Страница 49: ...45...

Страница 50: ...46...

Страница 51: ...47...

Страница 52: ...48...

Страница 53: ...49...

Страница 54: ...50...

Страница 55: ...51...

Страница 56: ...52...

Страница 57: ...53...

Страница 58: ...54...

Страница 59: ...55...

Страница 60: ...56...

Страница 61: ...57...

Страница 62: ...58...

Страница 63: ...59...

Страница 64: ...60...

Страница 65: ...61...

Страница 66: ...62...

Страница 67: ...63...

Страница 68: ...64...

Страница 69: ...65...

Страница 70: ...66...

Страница 71: ...67...

Страница 72: ...68...

Страница 73: ...69...

Страница 74: ...70...

Страница 75: ...71...

Страница 76: ...72...

Страница 77: ...73...

Страница 78: ...74...

Страница 79: ...75...

Страница 80: ...76...

Страница 81: ...77...

Страница 82: ...78...

Страница 83: ...79...

Страница 84: ...80...

Страница 85: ...81...

Страница 86: ...82...

Страница 87: ...83...

Страница 88: ...84...

Страница 89: ...85...

Страница 90: ...86...

Страница 91: ...87...

Страница 92: ...88...

Страница 93: ...89...

Страница 94: ...90...

Страница 95: ...91...

Страница 96: ...92...

Страница 97: ...93...

Страница 98: ...94...

Страница 99: ...97...

Страница 100: ...96...

Страница 101: ...97...

Страница 102: ...98...

Страница 103: ...99...

Страница 104: ...100...

Страница 105: ...101...

Страница 106: ...102...

Страница 107: ...103...

Страница 108: ...105...

Страница 109: ...105...

Страница 110: ...106...

Страница 111: ...107...

Страница 112: ...108...

Страница 113: ...109...

Страница 114: ...110...

Страница 115: ...111...

Страница 116: ...112...

Страница 117: ...113...

Страница 118: ...114...

Страница 119: ...115...

Страница 120: ...r time constant U15 USER 15 0 to 32767 _ 1 556 546 A U23 Integrall gain of continuous operation at power failure U23 USER 23 0 to 65535 _ 1 1738 1000 A U24 Proportionall gain of continuous operation a...

Страница 121: ...es Er6 When a component s Life expectancy time is reached an ON signal can be output However the inverter does not go into alarm and the fault relay does not change state 5 65 5 Function Selection F13...

Страница 122: ...by continuing the limiting action Torque limit operation regeneration avoidance operation and overcurrent limiting operation of 20ms or more This function selects the acceleration and deceleration pa...

Страница 123: ...ation ranges of S shape can be set up arbitrarily The range is the ratio for maximum output frequency 1 F03 or 2 A01 Setting range 1 to 50 100 value of this function means maximum frequency fmax Accel...

Страница 124: ...fan ON OFF control is used function code H 06 1 Turn off the power supply of inverter until the inverter and the cooling fan have stopped It is not necessary to remove an option card or control termi...

Страница 125: ...o smaller than factory set value This function becomes effective when function code F14 Restart mode after momentary power failure set value is 2 or 3 Setting range 0 65535 In case of F14 set value 2...

Страница 126: ...lection 5 70 U48 Input phase loss protection U 4 8 U S E R 4 8 U48 RS485 protocol selection U 4 9 U S E R 4 9 Set value Operation 0 Active without reactor ACR DCR 1 Active with reactor ACR DCR 2 Inact...

Страница 127: ...40 4R 25 8 8 50 2R 12 5 Set the function code both F13 and U59 before operating the inverter and don t change the functions during operation The integrated thermal data is cleared immediately when fun...

Страница 128: ...OFF while outputting alarm or run commmand or coast to stop command BX is ON when this adjustment is started the inverter displays the message Er7 TUNING ERROR 2 In this case start the self adjustment...

Страница 129: ...tion codes are not displayed All function codes F E C P H A U are displayed Existing function codes F E C P H A can be verified or copied New U User Function codes cannot be verified or copied IMO Jag...

Страница 130: ...126...

Страница 131: ...127...

Страница 132: ...128...

Страница 133: ...129...

Страница 134: ...130...

Страница 135: ...131...

Страница 136: ...132...

Страница 137: ...133...

Страница 138: ...134...

Страница 139: ...135...

Страница 140: ...136...

Страница 141: ...137...

Страница 142: ...138...

Страница 143: ...139...

Страница 144: ...140...

Страница 145: ...141...

Страница 146: ...142...

Страница 147: ...143...

Страница 148: ...144...

Страница 149: ...9 Specifications 9 1 9 Specifications 9 1 Standard Specifications 1 Three phase 400V series 9 145...

Страница 150: ...ltage is resumed Required power supply capability 8 2 2 3 1 9 4 19 28 1 Indicated capacities are at the rated output voltage 220V for the 200V series and 440V for the 400V series The rated capacity wi...

Страница 151: ...9 Specifications 9 3 9 147...

Страница 152: ...9 4 9 Specifications 9 148...

Страница 153: ...9 Specifications 9 5 9 149...

Страница 154: ...9 6 9 Specifications 9 VXM40 VXM75 VXM150 VXM400 VXM8A 2 VXM11A 2 VXM550 VXM750 VXM29A 2 VXM1100 VXM2200 VXM55A 2 VXM78A 2 150...

Страница 155: ...9 Specifications 9 7 9 Dimensions 30kW 220kW 151...

Страница 156: ...860 260 260 810 Inverter Type Dimensions mm Mtg Bolts Weight kg D D1 D2 D3 D4 D5 D6 C VXM280K 450 285 6 4 50 100 35 115 15 M12 250 VXM315K VXM400K 360 D D2 D1 D2 D1 D2 D1 W3 W4 W1 W3 W4 W1 W2 W3 W4 W...

Страница 157: ...9 Specifications 9 9 9 153...

Страница 158: ...154...

Страница 159: ...155...

Страница 160: ...156...

Страница 161: ...mensions of the filter Care should be taken to remove any paint etc from the mounting holes and face area of the panel This will ensure the best possible earthing of the filter 4 Use the screened cabl...

Страница 162: ...rent emissions for equipment having input currents up to and including 16A per phase The following products do not meet these limits unless fitted with the correct DC reactor VXM40 VXM75 If the DC rea...

Страница 163: ...r Max Rated Voltage Filter Type Rated Current Nominal leakage max leakage RFI filter 11 Electromagnetic compatibility EMC 11 3 Note Dimensions LxWxH mm Mount Dimms Y x X mm 0 75 1 45 2 5 5 0 5 0 5 5 8...

Страница 164: ...11 4 11 Electromagnetic compatibility EMC 11 160...

Страница 165: ...11 Electromagnetic compatibility EMC 11 5 11 161...

Страница 166: ...162 12 1...

Страница 167: ......

Страница 168: ...es Corner London NW2 7JP Telephone 44 0 20 8452 6444 Fax 44 0 20 8452 3512 Web www imopc com Email imo imopc com Out of hours telephone contacts Product Support UK South 07831 207220 Product Support U...

Отзывы: