Solar circulation unit available head.

Key:

  Vn  =  Available head

  An  =  Circulating pump absorbed power

Ci

rcu

la

to

r p

um

p a

bs

or

be

d p

ow

er (

W

)

Flow rate (l/h)

H

ea

d (kP

a)

1.12 COMMISSIONING.

Preliminary checks on the solar system

Before filling the hydraulic circuit and starting 

the system, carry out the following checks:

- ensure that the declaration of conformity of 

installation of the solar system is supplied with 

the appliance;

- make sure the safety devices are included and 

are operating properly, particularly:

  - safety valve (6 bar)
  - expansion vessel
  - thermostatic mixing valve
- make sure there are no leaks in the hydraulic 

circuit;

-  make sure there is an air vent valve positioned 

in the highest point of the circuit above the 

manifold and that it is operational.

- check connection to a 230V-50Hz power 

mains, correct L-N polarity and the earthing 

connection;

- Check that all the requirements relating to 

the boiler and the central heating circuit have 

been complied with, as described in the relative 

boiler instruction book.

If even only a single safety check offers a negative 

result, do not commission the system.

Expansion vessel factory-set pressure of the 

solar circuit hydraulic unit.

To compensate the high temperatures that can be 

reached by the liquid in the circuit and therefore 

its dilation, an expansion vessel has been fitted on 

the UB INOX SOLAR 200 ErP storage tank, with 

sufficient capacity to perform this task.

The expansion vessels are supplied factory-set at 

2.5 bar. It is therefore necessary to charge them to 

the pressure necessary for the circuit.
The expansion vessel must be charged to:

2 bar + 0.1 bar for every metre of the water 

column.

metre of the water column”

 means the vertical 

distance that is present between the expansion 

vessel and the solar manifold.

Example:

The circulation unit is found on the ground floor 

and the solar manifold is found on the roof at a 

hypothetical height of 6 m, the distance to be 

calculated is: 

6 m x 0.1 bar = 0.6 bar 

therefore the expansion vessel must be charged 

to:

2 + 0.6 = 

2.6 bar

Hydraulic unit safety valve.

There is a safety valve present on the hydraulic 

unit that protects the system from an excessive 

increase in pressure. This valve intervenes by 

discharging the liquid contained in the circuit 

when the pressure reaches 6 bar.

If the safety valve intervenes and therefore part of 

the liquid contained in the circuit is lost, it must 

be re-integrated.

1.13 FILLING THE SOLAR CIRCUIT 

SYSTEM.

The system can only be filled when:

- the system is completely assembled;
-  any operational residues have been eliminated 

that may cause obstructions and deteriorate the 

features of the glycol over time;

- any presence of water in the system has been 

eliminated, which could otherwise cause dam-

age to the system in winter;

-  the absence of leaks has been verified by checks 

using air;

- the storage tank unit has been filled;
-  the expansion vessel has been charged accord-

ing to system requirements.

The system must be filled only using the glycol 

supplied by Immergas via an automatic pump. 

The system must be filled with vent valve closed.

Proceed as follows to fill the system:

1 connect the flow pipe of the automatic pump to 

the fitting of the filling valve (9 Fig. 1-4) located 

under the pump and open the valve.

2 connect the return pipe of the automatic pump 

to the fitting of the draining valve (8 Fig. 1-4) 

and open the draining valve.

3 The flow-rate regulator screw (11 Fig. 1-4) must 

be orientated horizontally to ensure the closure 

of the integrated ball valve. Open the ball valve 

with thermometer (2 Fig. 1-4) above the pump.

4 Fill the filling pump tank with the amount of 

glycol necessary plus a minimum amount to 

be left on the bottom of the tank in order to 

prevent air circulating inside the circuit.

5 The filling stage must have a minimum dura-

tion of 20 ÷ 25 minutes. This time is required 

to completely remove all air from the circuit. 

Every now and again open the flow rate regula-

tor adjustment screw in order to eliminate air 

from inside (vertical position).

Содержание UB INOX SOLAR 200 ERP

Страница 1: ...UB INOX SOLAR 200 ERP Storage tank unit IE Instruction and recommendation booklet 1 038280ENG ...

Страница 2: ......

Страница 3: ...which has specific technical expertise in the system sector as required by Law Improper installation or assembly of the Immergas appliance and or components accessories kit and devices can cause unexpected problems to people animals and objects Read the instructions provided with the product carefully to ensure a proper installation Maintenance must be carried out by an authorised company The Auth...

Страница 4: ... pump solar heating system 8 1 12 Commissioning 9 1 13 Filling the solar circuit system 9 1 14 Solar control unit user instructions 10 1 15 Main components 13 1 16 Kits available on request 13 2 Use and maintenance instructions 14 2 1 Cleaning and maintenance 14 2 2 Emptying the storage tank unit 14 2 3 Cleaning the case 14 2 4 Decommissioning 14 2 5 Control panel 14 3 Checks and maintenance 15 3 ...

Страница 5: ...t operation turn the appliance off and contact an authorised company e g the Authorised Tech nical Assistance centre which has specifically trained staff and original spare parts Do not attempt to modify or repair the appliance alone Failuretocomplywiththeaboveimpliespersonal responsibility and invalidates the warranty Installation standards these storage tanks have been designed for floor install...

Страница 6: ... tank unit Attention after the connections have bee made the new system layout must be set on the solar control unit as follows press the i key for about 10 seconds use the scrolling keys to find parameter 27 system configuration press the i key for about 2 seconds upon accessing parameter 27 you will find that configuration 1 is set use the scrolling keys to select configuration 2 press the i key...

Страница 7: ...efer to the boiler instruction book 1 10 MAIN SOLAR CIRCULATION UNIT COMPONENTS The pump unit allows you to connect the storage tank to the solar manifold making the water cir culateaccordingtotherequestofthecontrolunit Hydraulic circuit resistance Head kPa Flow rate l h Head m c a A Storage tank unit hydraulic circuit resistance Key 1 Solar pump 2 Non return valve thermometer and cock 3 Valve dra...

Страница 8: ...ontrol to set advanced functions For proper op eration one must select the most suitable type of operation for the system and select a speed in the available range with a focus on energy savings Display of operation status During normal operation the status LED 2 is on green flashing FL when it is in stand by the four yellow LEDs 3 indicate circulator absorption according to the following table Ci...

Страница 9: ... the roof at a hypothetical height of 6 m the distance to be calculated is 6 m x 0 1 bar 0 6 bar therefore the expansion vessel must be charged to 2 0 6 2 6 bar Hydraulic unit safety valve There is a safety valve present on the hydraulic unit that protects the system from an excessive increase in pressure This valve intervenes by discharging the liquid contained in the circuit when the pressure re...

Страница 10: ...Otherwise press to exit In this case the value set will not be memorised but the previ ous one will be kept To exit the parameter menu press the button once or wait 60 seconds without press ing any keys 6 Eliminate any air in the solar circuit preferably using the so called pressure shot method which consists in raising the filling pressure of the circuit followed by a quick opening of the return ...

Страница 11: ...re C 90 160 C 140 C 18 Tank Maximum Temperature C 70 95 C 80 C 19 Value of the temperature differential between the solar collector maximum temperature PAR 17 and the solar collector temperature above which the solar collector cooling func tion activates Solar collector cooling function 0 Function deactivated 0 20 C 0 20 Diverter functioning 0 Off 1 Auto 2 On 0 2 1 21 Value of the Δ flow return te...

Страница 12: ...ly with return probe when Solar collector T solar collector return T PAR 21 Solar manifold anti freeze function The Solar Pump activates when Solar collector T PAR 23 The board will not deactivate the solar pump until Solar collector T PAR 23 1 C Attention the default anti freeze function is disabled PAR 23 0 Solar pump anti block function After 24 hours of inactivity the system pumps are activate...

Страница 13: ...s 16 Solar panel probe 17 Storage tank electric connections terminal board 1 16 KITS AVAILABLE ON REQUEST Recirculation kit on request The storage tank unit is prepared for application of the pump kit Immergas supplies a series of fittings and attachments that allow connection between the storage tank unit and domestic hot water system The pump kit attachment is also envi sioned on the template El...

Страница 14: ...horised local firm 2 2 EMPTYING THE STORAGE TANK UNIT To drain the storage tank use the special drain ing valve in the lower part of the storage tank Fig 1 12 part 8 Before draining ensure that the DHW inlet valve is closed 2 3 CLEANING THE CASE Use damp cloths and neutral detergent to clean the storage tank casing Never use abrasive or powder detergents 2 5 CONTROL PANEL Key 1 Solar control unit ...

Страница 15: ...filter 11 One way valve OV 15 Optional 12 Cold water inlet cock 13 One way solar valve 14 6 bar safety valve 15 Shut off valve with thermometer 16 Solar expansion vessel 17 Solar pump 18 Flow meter 19 Domestic hot water probe 20 Domestic hot water unabling probe 21 Stainless steel coil that can be coupled to solar panels 22 Solar system draining valve 23 Solar panel probe AC Domestic hot water out...

Страница 16: ...r the DHW regulation NTC probe Check the integrity of the storage tank Magne sium anode Check the state of the internal coil Check for any slurry deposits on the bottom of the storage tank Key A12 Solar management control unit B2 Domestic hot water probe NTC B11 Solar manifold probe PT1000 B12 Solar storage tank probe NTC B19 DHW inhibition probe NTC B20 Solar manifold return probe PT1000 Optional...

Страница 17: ...t models remove the lid 1 by pulling it upwards undo the screws 2 and pull the front panel outwards 3 undo the screws 4 of the sides 5 on the top and in the lower part of the sides themselves After having released them from the screws they can be removed by pulling them forward and then upwards 3 5 REPLACING THE ANODE Themagnesiumanodemustbereplacedannually Fig 1 12 part 5 present in the storage t...

Страница 18: ... l h 1140 1140 Coil head loss at 1000 l h kPa m H2 O 12 3 1 25 Central heating side maximum pressure bar 6 Central heating side maximum temperature C 90 Solar heat exchange maximum output kW 23 8 CH heat exchange maximum output kW 26 5 Full weight kg 310 67 Empty weight kg 106 1 Total water content l 204 57 Solar circuit maximum pressure bar 6 Total volume solar expansion vessel l 18 Solar expansi...

Страница 19: ...19 A B C D E F G 143W 200L F UB INOX SOLAR 200 ERP 3 7 PRODUCT SHEET IN COMPLIANCE WITH REGULATION 812 2013 ...

Страница 20: ...5 Inglese per IRLANDA IE Followus Immergas Italia immergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 ИЗКЛЮЧИТЕЛЕН ПРЕДСТАВИТЕЛ И СЕРВИЗ АМАКС ГАЗ ООД 1261 Мрамор София ул В Левски 148 Tel 0700 112 66 Fax 02 902 46 70 www amaxgas com ...

Отзывы: