1.4 CONNECTIONS.
Gas connection (Appliance category II
2H3+
).
Our boilers are designed to operate with methane
gas (G20) and LPG. Supply pipes must be the
same as or larger than the 3/4”G boiler fitting.
Before connecting the gas line, carefully clean
inside all the fuel feed system pipes to remove any
residue that could impair boiler efficiency. Also
make sure the gas corresponds to that for which
the boiler is prepared (see boiler data-plate). If
different, the appliance must be converted for
operation with the other type of gas (see conver-
ting appliance for other gas types). The dynamic
gas supply (methane or LPG) pressure must also
be checked according to the type used in the
boiler, as insufficient levels can reduce generator
output and cause malfunctions.
Ensure correct gas cock connection. The gas
supply pipe must be suitably dimensioned accor-
ding to current regulations in order to guarantee
correct gas flow to the burner even in conditions
of maximum generator output and to guarantee
appliance efficiency (technical specifications).
The coupling system must conform to standards.
Fuel gas quality.
The appliance has been desig-
ned to operate with gas free of impurities; other-
wise it is advisable to fit special filters upstream
from the appliance to restore the purity of the gas.
Storage tanks (in
case of supply from LPG
depot).
- New LPG storage tanks may contain residual
inert gases (nitrogen) that degrade the mixture
delivered to the appliance casing functioning
anomalies.
- Due to the composition of the LPG mixture,
layering of the mixture components may occur
during the period of storage in the tanks. This
can cause a variation in the heating power of
the mixture delivered to the appliance, with
subsequent change in its performance.
Hydraulic connection.
Important:
In order not to void the warranty
before making the boiler connections, carefully
clean the heating system (pipes, radiators, etc.)
with special pickling or de-scaling products to
remove any deposits that could compromise
correct boiler operation.
In compliance with Standards in force it is man-
datory to treat the water in the heating system
chemically in order to protect the system and
appliance from deposits of lime scale.
Hydraulic connections must be made in a
rational way using the couplings on the boiler
template. The boiler safety valves outlet must be
connected to a draining funnel. Otherwise, the
manufacturer declines any responsibility in case
of flooding if the drain valve cuts in.
In order to meet the system requirements
established by the regulations in terms of
pollution of drinking water, we recommend
installing the IMMERGAS anti-backflow kit to be
used upstream of the cold water inlet connection
of the boiler. It is also recommended that the heat
transfer fluid (e.g. water + glycol) entered in the
primary circuit of the boiler (heating circuit),
complies with the local regulations in force.
Important:
to preserve the duration of appliance
efficiency features, in the presence of water whose
features can lead to the deposit of lime scale,
installation of the “polyphosphate dispenser” kit
is recommended.
Electrical connection:
The “Maior Eolo” boiler
has an IPX5D protection rating for the entire
appliance. Electrical safety of the unit is reached
when it is correctly connected to an efficient
earthing system as specified by current safety
standards.
Important:
Immergas S.p.A. declines any
responsibility for damage or physical injury
caused by failure to connect the boiler to an
efficient earth system or failure to comply with
the reference standards.
Also ensure that the electrical installation corre-
sponds to maximum absorbed power specifications
as shown on the boiler data-plate. Boilers are sup-
plied complete with an “X” type power cable without
plug. The power supply cable must be connected to
a 230V ±10% / 50Hz mains supply respecting L-N
polarity and earth connection
. This network
must also have a multi-pole circuit breaker with
class III over-voltage category. When replacing the
power supply cable, contact a qualified technician
(e.g. the Immergas After-Sales Technical Assistance
Service). The power cable must be laid as shown.
In the event of mains fuses replacement on the
connection board, use a 3.15A quick-blow fuses.
For the main power supply to the appliance,
never use adapters, multiple sockets or exten-
sion leads.