Heating output.
calibrated in the central heating phase at nominal
output. It also has electronic modulation that
between the minimum heating output and the
maximum heating output depending on the
system's heating load.
N.B:
the selection of the “Minimum heating
output” and “Maximum heating output”
parameters, in the presence of a central heating
request, allows switch-on of the boiler and power
supply of the modulator with current equal to
the value of the respective parameter selected.
Minimum CH output
(continuous variation)
Flashing
LED (slow)
0% Imax. (Standard setting)
LED 2
7% Imax.
LED 3
14% Imax.
LED 4
21% Imax.
LED 5
28% Imax.
LED 6
35% Imax.
LED 7
42% Imax.
LED 8
49% Imax.
LED 9
56% Imax.
LED 10
63% Imax.
LED 11
Maximum power
central heating
(continuous variation)
Flashing
LED (slow)
0% Imax.
LED 2
11% Imax.
LED 3
22% Imax.
LED 4
33% Imax.
LED 5
44% Imax.
LED 6
55% Imax.
LED 7
66% Imax.
LED 8
77% Imax.
LED 9
88% Imax.
LED 10
100% Imax. (Standard setting)
LED 11
Permanent reduction of the timer.
has electronic timing, which prevents the burner
e boiler has a standard supply of a timer
adjusted at 180 seconds.
Heating switch-on timer
(continuous variation)
Flashing
LED (slow)
30 seconds
LED 2
55 seconds
LED 3
80 seconds
LED 4
105 seconds
LED 5
130 seconds
LED 6
155 seconds
LED 7
180 seconds (Standard setting)
LED 8
205 seconds
LED 9
230 seconds
LED 10
255 seconds
LED 11
Central heating ramp timing.
e boiler
distributes he maximum power set in the
previous parameter. e boiler performs an
ignition ramp of about 650 seconds to arrive
from minimum power to nominal heating power.
Central heating ramp timer
(continuous variation)
Flashing
LED (slow)
65 seconds
LED 2
130 seconds
LED 3
195 seconds
LED 4
260 seconds
LED 5
325 seconds
LED 6
390 seconds
LED 7
455 seconds
LED 8
520 seconds
LED 9
585 seconds
LED 10
650 seconds (Standard setting)
LED 11
Heating switch-on delay request from Room
thermostat and Comando Amico Remoto
remote control
V2
(CAR
V2
).
case of particular systems (e.g. area systems with
motorised thermostatic valves etc.) it may be
necessary to delay ignition.
Heating switch-on delay
request from Room
thermostat and CAR
V2
(continuous variation).
Flashing
LED (slow)
0 seconds (Standard setting)
LED 2
57 seconds
LED 3
113 seconds
LED 4
170 seconds
LED 5
226 seconds
LED 6
283 seconds
LED 7
340 seconds
LED 8
396 seconds
LED 9
453 seconds
LED 10
510 seconds
LED 11
DHW thermostat.
With the “correlated”
takes place on the basis of the temperature set
using the domestic hot water adjustment selector
DHW thermostat
Flashing
LED (slow)
Correlated (Standard setting)
LED 2
Fixed
LED 11
Circulating pump function.
Two circulating
pump operational modes can be selected in
heating phase.
In “intermittent” mode it is activated from
the room thermostat or from the Comando
Amico Remoto
V2
(CAR
V2
) remote control, in
“continuative” mode the pump always functions
when the main switch (12) is on heating mode.
Pump function
Flashing
LED (slow)
Intermittent (Standard setting)
LED 2
Continuous
LED 11
Town Gas G110 – Industrial gas.
of this function is used to adjust the boiler in
Town Gas G110 - Industrial
Flashing
LED (slow)
LED 2
On
LED 11
MAX POWER CENTRAL HEATING
(continuous variation)
FLASHING LED (SLOW)
0% Imax.
13.4
LED 2
11% Imax.
15.7
LED 3
22% Imax.
18.1
LED 4
33% Imax.
20.5
LED 5
44% Imax.
22.9
LED 6
55% Imax.
25.3
LED 7
66% Imax.
27.6
LED 8
77% Imax.
30.0
LED 9
88% Imax.
32.4
LED 10
100% Imax. (Standard setting)
35.0