2.2  PRODUCT INSTALLATION.

1 -  Take the water heater to the place of installa-

tion.

2 - Open the packaging.
3 -  Separate the water heater from the pallet and 

place it next to the hydraulic connection.

The water heater must be installed on a 

smooth and level surface (± 1°)

.

If the surface is not level, the position  

must be adjusted using the levelling feet.

Unless this is done, there could be problems 

with removal of condensates, leading to 

icing up.

It is a mandatory requirement (in accordance 

with article 20 of EN 60335-1) for the boiler 

to be secured to the floor using the fixing 

attachments provided (Fig. 2-5).

4 - Adjustment of air intake and outlet vents.

  • Remove the screws from behind each of the 

adjustable outlets, with a screwdriver (Fig. 

2-6).

  • After removing the clamping screws, the 

outlets may be rotated (through 360°) to help 

install the product (Fig. 2-7).

  • To aid correct positioning of the ducts on 

the adjustable outlets, a specific position is 

required (Fig. 2-8) to extract the outlets from 

their housing.

N.B.:

 the configuration shown in Fig. 2-10 is 

forbidden: the device draws in the exhaust air, 

which is colder.

This phenomenon, called recirculation, signifi-

cantly reduces the performance of the appliance.

2.3  HYDRAULIC CONNECTION.

Connection to the cold water inlet.

Before connecting the water system, it is essen-

tial to clean the pipes thoroughly, to avert the 

risk of any metal or other particles entering the 

boiler tank.

It is mandatory to install a safety device, set to 

be triggered at 0.7 MPa (7 bars) (not supplied 

with the water heater), sized 3/4”, compliant with 

standard EN1487 as amended and added, and in 

any case compliant with local regulations in force: 

this safety device is to be fitted to the cold water 

inlet of the water heater and must be protected 

against freezing.

Note:

 no hydraulic fittings (stop valve, pressure 

reducer, etc.) must be placed between the safety 

unit and the cold water inlet of the water heater, 

except for a copper pipe.

Connect the safety device to a drain pipe kept in 

the open air, in a frost-free environment, with 

a permanent downward gradient, to remove 

any expansion water generated by the heating 

process or drainage water coming from the water 

heater itself.

The pipes used must withstand a temperature of 

85°C and a pressure of 1 MPa (10 bar).

When the inlet water pressure exceeds 0.5 MPa (5 

bar), a pressure reducer is required (not supplied 

as standard).

The pressure reducer must be installed at the 

beginning of the main distribution network

.

A pressure of 0.3 to 0.4 MPa (3 and 4 bar) is 

recommended.

Connection to the hot water inlet.

Note:

 do not connect the hot water directly to 

copper pipes, in order to avoid copper/iron gal-

vanic coupling (risk of corrosion). It is therefore 

obligatory to fit a dielectric fitting on the hot wa-

ter outlet (supplied with the appliance) (Fig. 2-9).

Any corrosion on the threads of the hot water 

outlet fitting, due to failure to use the fitting 

supplied, shall void product warranty

.

In the event pipes in synthetic material have been 

used (e.g.: PER, multilayer...), we strongly recom-

mend installing a thermostatic control device 

at the exit side of the water heater and set it ac-

cording to the performance of the material used.

PLUMBING CONNECTIONS FOR COIL 

VERSION.

Especially for Rapax 300 V3 the use of recircula-

tion is not recommended; this type of installation 

may cause water destratification in the tank, 

leading to increased use of the heat pump and 

electrical resistor.

Connection to the recirculation fitting.

N.B.:

 do not connect the recirculation fitting 

directly to copper pipes, in order to avoid cop-

per/iron galvanic coupling (risk of corrosion). 

It is therefore mandatory to mount a dielectric 

system to the recirculation fitting (not supplied 

as standard with the device).

Any corrosion on the threads of the recircu-

lation fitting, due to failure to use the above 

fitting, shall void product warranty

.

N.B.:

 if recirculation is not used, close the fitting 

with the “cap + gasket” set (supplied with the 

appliance).

Connection of the primary circuit of the boiler.

N.B.:

 protect from overpressure caused by water 

expansion during heating with a 0.3 MPa (3 bars) 

valve, and with a closed diaphragm expansion 

vessel (if not fitted in the boiler). The operating 

pressure of the circuit must not exceed 0.3 MPa 

(3 bars), and its temperature must not be higher 

than 85°C.

Содержание 3.030072

Страница 1: ...RAPAX 200 V3 RAPAX 200 SOL V3 RAPAX 300 V3 RAPAX 300 SOL V3 IE Instructions and warnings Installer User Maintenance technician 1 043869ENG 1 043869ENG...

Страница 2: ...alve 7 Fan 8 Compressor 9 User terminal board 10 Immersion heater 11 Domestic hot water sensor 12 High pressure sensor 13 Compressor protection thermostat 14 Compressor engage condenser Colour code ke...

Страница 3: ...ed by excessive pressure due to the safety valve blocking because of ice Ensuretheflooronwhichthe appliance is to be installed is suitable to withstand the appliance s own weight and that of the water...

Страница 4: ...exceed 0 3 MPa 3 bars and its max temperature must not exceed 85 C To perform any discharge operations of the water heater strictlyadheretothefollowing sequence disconnect the appliance from the elect...

Страница 5: ...ntenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by professionally qualified staff intended as staff with specific technical skil...

Страница 6: ...d components 8 2 Installation 10 2 1 Choosing the place of installation 10 2 2 Product installation 13 2 3 Hydraulic connection 13 2 4 Air intake connection 14 2 5 Electrical connection 14 2 6 Electri...

Страница 7: ...ified staff only POSITIONS ALLOWED DURING TRANSPORT POSITIONS NOT ALLOWED DURING TRANSPORT Technical characteristics Unit of measurement Rapax 200 V3 Rapax 200 SOL V3 Rapax 300 V3 Rapax 300 SOL V3 Dim...

Страница 8: ...urn to solar panels Rapax Sol V3 model only SC Condensate drain 20 RC 3 4 M Recirculation Rapax Sol V3 model only Ref Description Rapax 200 V3 Rapax 200 Sol V3 Rapax 300 V3 Rapax 300 Sol V3 A Condensa...

Страница 9: ...piral unit 9 Fan 10 Spiral elastic 11 Terminal board unit Not shown manual dielectric connection con densate draining pipe safety unit 12 Front cover 13 Compressor 14 Compressor coating 15 Compressor...

Страница 10: ...ferably insulated from the home s heated rooms Recommended room underground or base ment room where the temperature is higher than 10 C all year round garage boiler room with the exception of rooms wh...

Страница 11: ...and recovery of waste calories from washing machines and tumble dryers Room in basement recovery of free calories released by the floor and walls of the base ment 2nd configuration installation in a h...

Страница 12: ...y harmful for the duration in service of your water heater Connection to an attic In the presence of inadequate insulation between the building and the relative attics this type of installation may in...

Страница 13: ...th a permanent downward gradient to remove any expansion water generated by the heating process or drainage water coming from the water heater itself The pipes used must withstand a temperature of 85...

Страница 14: ...ductors with 2 5 mm section Installation shall consist of a circuit breaker or 16A multi pole fuse with contacts compliant with regulations in force A 30 mA differential circuit breaker If the power c...

Страница 15: ...15 2 11 2 12 The ducts must be fitted to the adjustable air intake and outlet vents Specific cable duct...

Страница 16: ...B B2 DHW probe K1 Domestic hot water unabling relay R1 Resistance 2 2 K Key A3 Integrated P C B B2 DHW probe N B With this configuration the boiler can show an error on the domestic probe Power suppl...

Страница 17: ...e screen Follow the on screen instructions carefully to set parameters date and time air ducts language recirculation photovoltaic operating time slots anti legionella system After setting the paramet...

Страница 18: ...1 Flat solar collectors 2 Electronic control unit 3 solar unit single circulation 4 Expansion vessel 5 Safety valve 6 System probe and venting unit 7 Mixing valve 8 Rapax Sol V3 Water heater 9 Non ret...

Страница 19: ...sumes operation with the initial settings The BOOST can be interrupted at any time Pause the BOOST OPERATING mode Choose the operating mode Select AUTO or MANUAL see paragraph 3 6 Operating modes ABSE...

Страница 20: ...ate or not the electrical integration support If it is off the device will never use the electrical integration in case of low temperatures a shortage of hot water is possible 3 6 SELECTING THE OPERAT...

Страница 21: ...temperature in the tank Our product permanently calculates depending on the air temperature and the water temperature which energy is cheaper This SMART Energy function can decide to start heating wi...

Страница 22: ...ing Fill the water heater by leaving a hot water tap open if the water flows it indicates that the water heater is full Check the water tightness of the seal and only then replace the thermostat and i...

Страница 23: ...or out of measurement range from 20 to 110 PDC stoppage Central heating C H in ELEC Check the connections reference A4 and the correct application of the probe on the pipe Check the fan operation and...

Страница 24: ...aporator works on the fan works on the compressor etc N B it is essential to disconnect the power cable on the terminal board so that the rear cover of the heat pump can be removed Fig 4 2 Remove the...

Страница 25: ...an the filter see maintenance chapter Encrusted water heater Descale the water heater Continued water leak to the level of the safety unit outside the heating period Safety valve damaged or clogged Re...

Страница 26: ...f calibration etc Insulating sheath cast iron steel or insulat ing missing on hot water connection pipes which could cause their corrosion Faulty electrical connection incorrect earth ing inadequate c...

Страница 27: ...ditions 116 Energy efficiency in colder climate conditions 96 Energy efficiency in warmer climate conditions 130 Annual energy consumption in average climate conditions 883 kW h Annual energy consumpt...

Страница 28: ...iency in colder climate conditions 100 Energy efficiency in warmer climate conditions 141 Annual energy consumption in average climate conditions 1334 kW h Annual energy consumption in colder climate...

Страница 29: ...al energy efficiency after installation since such efficiency is affected by additional factors such as the heat loss in the distribution system and the size of the products compared to the size and f...

Страница 30: ...38 40 39 50 55 60 65 75 80 85 100 115 123 131 130 150 160 170 163 188 200 213 M L XL XXL 3 2 3 2 The energy efficiency of the set of products indicated in this sheet may not reflect the actual energy...

Страница 31: ...31...

Страница 32: ...llo RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper This instruction booklet is made of ecological paper Cod 1 043869ENG rev ST...

Отзывы: