1.8  IMMERGAS FLUE SYSTEMS.

Immergas supplies various solutions separately 

from the boilers regarding the installation of 

air intake terminals and flue exhaust, which are 

fundamental for boiler operation.

Attention: the boiler must be installed ex-

clusively with an original Immergas “Green 

Range” inspectionable air intake device and 

fumes extraction system made of plastic, as 

required by the regulations in force.
The plastic pipes cannot be installed outdoors, 

for tracts longer than 40 cm, without suitable 

protection from UV rays and other atmos-

pheric agents.
This system can be identified by an identifica-

tion mark and special distinctive marking 

bearing the note: “only for condensing boilers”.

•  Resistance factors and equivalent lengths. Each 

flue component has a 

Resistance Factor

 based 

on experimental tests and specified in the table 

below. The Resistance Factor for individual 

components is independent from the type of 

boiler on which it is installed and has a dimen-

sionless size. It is however, conditioned by the 

temperature of the fluids that pass through the 

pipe and therefore, varies according to applica-

tions for air intake or flue exhaust. Each single 

component has a resistance corresponding to 

a certain length in metres of pipe of the same 

diameter; the so-called 

equivalent length

can be obtained from the ratio between the 

relative Resistance Factors. 

All boilers have an 

experimentally obtainable maximum Resistance 

Factor equal to 100.

 The maximum Resistance 

Factor allowed corresponds to the resistance 

encountered with the maximum allowed pipe 

length for each type of Terminal Kit. This 

information allows calculations to be made to 

verify the possibility of setting up various flue 

configurations.

• 

Positioning the gaskets (black) for “green 

range” flue systems.

 Position the gasket cor-

rectly (for bends and extensions) (Fig. 1-6):

  - gasket (A) with notches, to use for bends;
  -  gasket (B) without notches, to use for exten-

sions;

 N.B.:

 if component lubrication (already car-

ried out by the manufacturer) is not sufficient, 

remove the residual lubricant using a dry cloth, 

then to ease fitting coat the parts with talc, sup-

plied in the kit.

• Coupling extension pipes and concentric 

elbows. To install push-fitting extensions with 

other elements of the flue, proceed as follows: 

Install the concentric pipe or elbow with the 

male side (smooth) on the female side (with lip 

seal) to the end stop on the previously installed 

element in order to ensure sealing efficiency of 

the coupling.

 

Attention:

 if the exhaust terminal and/or 

concentric extension pipe needs shortening, 

consider that the internal duct must always 

protrude by 5 mm with respect to the external 

duct.

• 

N.B.:

 for safety purposes, do not obstruct the 

boiler intake/exhaust terminal, even temporar-

ily.

• 

N.B.:

 when installing horizontal pipes, a mini-

mum inclination of 3% must be maintained and 

a section clip with pin must be installed every 

3 metres.

1.9  TABLES OF RESISTANCE FACTORS 

AND EQUIVALENT LENGTHS.

TYPE OF DUCT

Resistance

Factor

(R)

Equivalent length 

in m of concentric 

pipe Ø 80/125

Concentric pipe Ø 80/125 m 1

2.1

1

Concentric bend 90° Ø 80/125

3.0

1.4

Concentric bend 45° Ø 80/125

2.1

1

Terminal complete with concentric 

horizontal intake-exhaust Ø 80/125

2.8

1.3

Terminal complete with concentric 

vertical intake-exhaust Ø 80/125

3.6

1.7

Concentric bend 90° Ø 80/125 with 

inspection

3.4

1.6

Stub pipe with inspection Ø 80/125

3.4

1.6

Содержание 3.025615

Страница 1: ...MAGIS VICTRIX ERP IE Instruction and recommendation booklet 1 038946ENG...

Страница 2: ......

Страница 3: ...fessionals within the dimensional limits established by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions...

Страница 4: ...2 5 Using the boiler 24 2 6 Troubleshooting 25 2 7 Parameters and information menu 27 2 8 Boiler shutdown 28 2 9 Restore central heating system pressure 28 2 10System drainage 28 2 11Anti freeze prot...

Страница 5: ...damaged if the safety valve intervenes with an obstructed conveying system the safety valve must be conveyed away by a draining funnel or if there are leaks from the hydraulic connections on the contr...

Страница 6: ...be followed scrupulously regarding the percentage neces sary with respect to the minimum temperature at which the system must be kept An aqueous solution must be made with potential pollu tion class o...

Страница 7: ...escopic fitting 3 4 R RHT MHT M N 1 Rubber fitting for condensate drainage SC N 1 Condensate drainage corrugated pipe SC N 1 Extension for filling valve N 1 Filling valve N 1 Condensation collection t...

Страница 8: ...ecial pickling or descaling products to remove any deposits that could compromise correct boiler operation A chemical treatment of the thermal system wa ter is required in compliance with the technica...

Страница 9: ...r is made using wires with a minimum section of 0 50 mm2 and maximum section of 2 5 mm2 and with a maximum length of 50 metres External temperature probe electrical con nection Theboileronlyworksifiti...

Страница 10: ...pipe length for each type of Terminal Kit This information allows calculations to be made to verify the possibility of setting up various flue configurations Positioning the gaskets black for green ra...

Страница 11: ...Intake and Exhaust 16 3 m 2 5 Intake m 18 7 Exhaust m 4 9 m 7 7 Exhaust m 13 6 Concentric vertical intake exhaust terminal 60 100 Intake and Exhaust 9 m 1 4 Intake m 10 3 Exhaust m 2 7 m 4 3 Exhaust m...

Страница 12: ...ent in the kit positioning the relevant gaskets Engage the 90 80 bend with the male end smooth in the female end with lip seal of the 80 flange unit until it stops Introduce the gasket making it run a...

Страница 13: ...orizontal m in cluding the terminal with grid and excluding the concentric bend leaving the boiler This configurationcorrespondstoaresistancefactor of 100 In this case the special extensions must be r...

Страница 14: ...cal length of 14 4 m including the terminal This configuration corresponds to a resistance factor of 100 In this case specific extensions must be requested Vertical kit with aluminium tile 80 125 Kit...

Страница 15: ...th the male side smooth in the female side of the bend 5 up to the end stop ensuring that the internal and external wall sealing plates are fitted Fit the exhaust pipe 9 with the male side smooth to t...

Страница 16: ...ical data The dimensions of the shafts must ensure a minimum gap between the outer wall of the smoke duct and the inner wall of the shaft 30 mm for circular section shafts and 20 mm in the event of a...

Страница 17: ...th is obtained considering the complete 80 exhaust terminal 1m of 80 pipe in ex haust two 90 80 bends on the boiler outlet 1 16 CONFIGURATION TYPE B OPEN CHAMBER AND FAN ASSISTED FOR INDOORS The appli...

Страница 18: ...ns featured on the boiler active upon initial ignition and on the heat pump see relative instructions booklet Vent the boiler circulation pump by loosening the front cap and keeping the motor running...

Страница 19: ...level from a minimum one to a maximum one by turning the selector switch clockwise in the relative power scale Proportional head program P V 3 fig 1 25 This allows the pressure level head to be propo...

Страница 20: ...functioning characteristics of the boiler thanks to its inspectionable filter Kit with two motorised areas on request In the event one wants to divide the thermal sys tem in two areas to interlock the...

Страница 21: ...on module 14 Manual air vent valve 15 Negative signal pressure point 16 Positive signal pressure point 17 Sample points air A flue gas F 18 Flue safety thermostat 19 Heat exchanger safety thermal fuse...

Страница 22: ...d to weathering rain sunlight etc the appliance power cable must not be re placed by the user if the cable is damaged switch off the ap pliance and solely contact an authorised company to replace it i...

Страница 23: ...fter a request for domestic hot water or central heating in order to evacuate residual flue gas F5 Postcirculation in progress Pump in function after a request for domestic hot water or central heatin...

Страница 24: ...ting stage if the water temperature is sufficient to heat the system the boiler can operate just with the activation of water circulation Winter operation mode with room central heating with boiler 2...

Страница 25: ...on circuit or anomaly in the flame control unit Press the Reset button 1 2 23 Return probe anomaly The board detects an anomaly on the system return NTC probe The boiler does not start 1 2 24 Push but...

Страница 26: ...g and cooling are inhibited Check the type of anomaly directly on the remote panel display see relative instruc tions manual In the event the heat pump does not fea ture any anomaly check that the dom...

Страница 27: ...ntenance chapter By turning the central heating temperature se lector switch 3 scroll through the menu items By pressing button D access the various levels of the menu and the choice of parameters is...

Страница 28: ...Victrix ErP series boiler features an anti freeze function that lights the burner automatically when the temperature falls below 4 C standard protection up to minimum tem perature of 3 C All informat...

Страница 29: ...omestic hot water check sealing efficiency of water circuits check ventilation and or aeration of the instal lation room where provided If even only a single safety check offers a negative result do n...

Страница 30: ...re point 22 Flue sample point 23 Fumes hood 24 Heat exchanger safety thermal fuse 25 Delivery probe 26 Safety thermostat 27 Ignition electrodes 28 Burner 29 Condensation module cover 30 Return probe 3...

Страница 31: ...tle water circulation in the system or blocked pump Check on the manometer that the system pressure is within established limits Check that the radiator valves are not closed and also the functionalit...

Страница 32: ...in the table Par 3 20 3 6 CALIBRATION OF NUMBER OF FAN REVS Attention verification and calibration is neces sary in the case of transformation to other types of gas in the extraordinary maintenance ph...

Страница 33: ...ating selector switch to maxi mum turn it in a clockwise direction until 99 is seen on the display To have an exact value of CO2 in the flue gases the technician must insert the sampling probe to the...

Страница 34: ...efines the maximum flow tempera ture corresponding to operation with minimum external temperature see graph Fig 1 5 it can be set between 50 C and 85 C N B to continue one must confirm the parameter p...

Страница 35: ...to automatic functioning therefore with variable flow rate Open adjuster completely open therefore maximum flow rate available 09 L M 12 L M and 15 L M operation with defined flow AUTO RELAY1 RELE1 0...

Страница 36: ...event the boiler circulator pump is replaced with a traditional fixed speed circulator pump one must connect the new circulator pump to the relay board P76 15 C 14 C CE With S34 On If the reading of...

Страница 37: ...HEATING OPERATION IN COMBINATION WITH THE HEAT PUMP Following a request during the room heating mode the electronics decide according to the external temperature whether to activate the heat pump or w...

Страница 38: ...han that set by the do mestic hot water selector switch SET the boiler does not switch on 3 18 YEARLY APPLIANCE CHECK AND MAINTENANCE The following checks and maintenance should be performed at least...

Страница 39: ...screws 11 disassemble the front 1 of the boiler by loos ening the screw 2 by 1 4 turn push the front upwards while pulling it towards you at the same time to release it from the side 3 and upper 4 ho...

Страница 40: ...17200 2 16 3 48 35 5 1 61 3 40 34 7 1 58 4 54 46 3 19 0 16340 2 05 3 17 32 3 1 53 3 10 31 6 1 50 4 15 42 4 18 0 15480 1 94 2 87 29 3 1 45 2 81 28 6 1 42 3 79 38 7 17 0 14620 1 84 2 59 26 5 1 37 2 53...

Страница 41: ...ss at casing with burner On Off 80 60 C 0 49 0 70 Heat loss at flue with burner On Off 80 60 C 0 02 1 90 Central heating circuit max operating pressure bar 3 Maximum heating temperature C 90 Adjustabl...

Страница 42: ...r N Serial Number CHK Check Cod PIN PIN code Type Type of installation ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn max CH maximum heat...

Страница 43: ...0 071 kW At partial load elmin 0 010 kW Ignition burner energy consumption Pign 0 000 kW In standby mode PSB 0 005 kW Emissions of nitrogen oxides NOX 23 mg kWh For mixed central heating appliances St...

Страница 44: ...ementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at 35 C F...

Страница 45: ...e energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by further fac...

Страница 46: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 47: ...ncy under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxiliary electricity...

Страница 48: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038946ENG rev ST 002042 001 06 19 Inglese p...

Отзывы: