TA-SCOPE
26
Balancing
14
After the calibration cycle is done the measurement begins and values for the connected valve are displayed.
15
Press function key
Continue
.
16
Shut the valve and then press the function key
Done
.
17
Values for the closed valve are displayed. Press function key
Continue
.
18
Re-open the valve to the previous setting as displayed and press function key
Continue
.
19
The selected module appears on the display. Navigate
to the next valve you wish to measure. Press function
key
Measure
and repeat the process from item 11.
20
Continue to measure all valves in the module until they are all marked with a green tick. Follow the sequence as
above and instructions on the display. To check current status of the valves in the module press
View measured
data
from the
Options
menu.
21
When all valves in the chosen module are measured select
Calculate
from the
Options
menu.
22
A table of diagnosed Differential Pressures (Dp) in the module is displayed on screen. The diagnosed Differential
Pressures correspond to the pressure drops that will happen in each circuit and distribution pipe segment
(return) when design flows will be obtained in all circuits.
23
Navigate
in the diagnostic table to compare the diagnosed values to the design Differential Pressures (Dp) if
you have downloaded a calculated hydronic network from HySelect. Press function key
Continue
.
24
Calculated setting for each valve in the module are shown in a list, adjust the valves accordingly.
25
Repeat the balancing process as above (item 6-24) for each module in the Hydronic Network.
26
To verify the completeness of the balancing process a control measurement of each valve should be performed.
27
The collected data from the control measurement can be uploaded to HySelect and used for a Balancing report.
Balance a Hydronic Network with TA-Wireless
The TA-Wireless method makes use of wireless technology and simultaneous measurement with two Dp sensors
for balancing a hydronic network. It minimizes the number of access to each balancing valve. Required equipment
is two Dp sensors and two or more long distance transmission relays (required for balancing inside buildings over
more than 20-30 m or across multiple floors).
When balancing a predefined hydronic network the action can be started either from the Balancing function, as
described below, or directly from the function Hydronic Networks, see page 23. The method and required actions
are then the same.
1
Select
Balancing
from the main menu, press enter.
2
If required, adjust the acceptable flow deviations in design conditions with
Balancing Tolerance
(also available in
Settings
menu, see page 37).
3
Select
TA-Wireless method
. Press enter.
4
A general description of the TA-Wireless method is displayed. Press function key
Continue
.
5
A drop-down list of networks stored in your TA-SCOPE is displayed. Navigate
to desired network and press
enter. If no Hydronic Network is stored the only available option is
New Hydronic Network
.
6
Select
An existing module,
press enter.
7
The selected network appears on the display. Expand
the network and navigate
to the module where the
balancing should start from.
8
Ensure the essential balancing prerequisites displayed in the list are fulfilled, press function key
Continue
.
9
A list of options appears on the display. Select
Perform Balancing
and press enter.
Tips!
Make sure that you have two Dp sensors available and that your TA-SCOPE is set in
two Dp sensors mode before starting balancing with the TA-Wireless method, see Wireless
signal on page 37.
!