TA-SCOPE
21
Measure Power
TA-SCOPE contains a method for measuring power. Depending on the type of circuit, i.e., number of measuring
points available, the function is performed in various ways. Follow the detailed instructions on the display.
1
Navigate
to
Quick Measure
in the main menu and press enter.
2
Navigate
to
Measure Power
and press enter.
3
Meas. configuration
– State available measuring equipment.
4
State number of available measuring points. Connect the measuring needles and sensor(s), see page 15.
5
TA-SCOPE automatically checks if the correct set of sensors are connected according to selected measurement
configuration.
6
If power measurement can be performed at once follow the instructions below. An alternative instruction will be
displayed if not enough temperature probes or measuring points are available for measuring power in one step.
7
Optionally input
Design Flow
. Navigate
to and type the given design flow for the terminal. While
measuring the deviation is given as a percentage besides the entered design flow.
8
Define valve
. Navigate
to
and press enter.
9
Select input field for
Type
and press enter.
10
Navigate
to desired valve type and press enter.
11
Continue by defining
Family
and
Valve
in the same way.
12
Make valve settings valid by pressing the function key
Done
. Valve settings are visible in the
Measure Flow
menu. Valve size can easily be changed from here, navigate
to
and cycle
the options. Type and
family stays the same.
13
Input
Valve Opening
. Navigate
to
and type the number of turns stated at the digital read-out at the
handwheel, more handwheel details on page 16.
14
Define fluid in
. Press enter and navigate
to input fluid temperature and properties. Press enter.
15
Freezing point is stated below the temperature input field and the auto correction function indicates if the allowed
limits are exceeded. More
Fluid
details on page 34.
16
Press function key
Done
to make fluid definition valid.
17
Press function key
Measure
to start measuring.
18
After the calibration cycle is done the measurement begins and values are displayed for Power, Flow and
Differential Temperature ∆T.
19
Press function key
Hold
to pause the measuring, and press
Continue
to resume.
20
Possible to save measuring data in the same way as Flow, see item 18 (page 18) in the
Measure flow
section.
21
End measurement by exiting the menu, press and disconnect the measuring points according to page 15.
Quick Measure