Loopback testing is useful for troubleshooting problems with network connections 
should they occur.  Looping received data back onto the transmit path helps 
determine whether a connection is still valid.  Remote loopback tests isolate problems 
on the coax run between an iMcV-DS3/E3-LineTerm module and the connected 
device, while local loopback tests can isolate problems on the fiber connected to the 
module. 

The following illustrations show a typical progression of loopback tests (i.e., starting by 
checking the coax segment at the local side, then the fiber segment at the remote 
side, etc). 

 

 

 

 

Содержание iMcV-DS3/E3-LineTerm

Страница 1: ...iMcV DS3 E3 LineTerm Operation Manual ...

Страница 2: ...nger To receive in warranty service the defective product must be received at IMC Networks no later than the end of the warranty period The product must be accompanied by proof of purchase satisfactory to IMC Networks denoting product serial number and purchase date a written description of the defect and a Return Merchandise Authorization RMA number issued by IMC Networks No products will be acce...

Страница 3: ...3 LineTerm 1 Configuration 1 Prerequisites 1 Managed Modules 2 Unmanaged Modules 2 DIP Switches 2 DIP Switch Settings 3 Features 3 Installation 6 LED Operation 6 Loopback Testing 7 Pseudorandom Bit Sequence PRBS Testing 9 Installation Troubleshooting 10 General Information 11 Safety Certifications 12 ...

Страница 4: ...m and 1550 nm to share one fiber strand essentially doubling the capacity of installed fiber The single strand versions at HOST and REMOTE must have opposite transmit and receive wavelengths For example one that transmits at 1310 nm must be paired with another that receives at 1310 nm iMcV DS3 E3 LineTerm modules must be deployed in pairs one at each end of a fiber line The data transmitted on the...

Страница 5: ...rements for the installation NOTE IMC Networks iView2 software is also available for downloading please visit www imcnetworks com iView2 supports the following platforms Windows 98 Windows NT Windows 2000 Windows XP Windows Vista In addition there are Java versions of iView for other Java capable operating systems such as Linux Unmanaged Modules Before installing the module in an unmanaged chassis...

Страница 6: ... OFF Pseudorandom Bit Sequence DS3 E3 STS 1 Selection S1 8 ON 9 OFF 45 Mbps DS3 D S1 8 OFF 9 ON 34 Mbps E3 S1 8 ON 9 ON 52 Mbps STS 1 Remote Management S1 10 OFF Remote Management Disabled D S1 10 ON Remote Management Enabled Features The iMcV DS3 E3 LineTerm module includes several features that allow it to be configured for DS3 E3 or STS 1 based environments Loopback DIP Switch S1 Position 1 Thi...

Страница 7: ...the fiber link and lights the LOS LED The module then responds by sending a Remote Alarm Indication RAI signal back to the Fiber line turning ON the RAI LED at the far end of the line and sending AIS to the COAX Port The RAI LED is now ON at the source of the Fiber fault By using the Fault Loopback Function a local site administrator can quickly determine where a fiber fault is located from either...

Страница 8: ...ata rate to use on the coax line The data rate selections available include the following DS3 44 736 Mbps 20 ppm E3 34 368 Mbps 20 ppm STS 1 51 840 Mbps 20 ppm By default this feature is set to DS3 This feature can be selected only by setting the DIP switches manually Remote Management DIP Switch S1 Position 10 This switch enables or disables the Remote Management mode Enabling Remote Management o...

Страница 9: ...pport positive referenced ground systems typically used in Telco environments The IE MediaChassis 2 DC and the iMediaChassis 6 DC are suitable alternatives LED Operation The iMcV DS3 E3 LineTerm module features several diagnostic LEDs per port The LED functions are LEDs Next to Coax BNC Port ER Flashes yellow whenever a line code violation is received LOS Glows red when the BNC is receiving no sig...

Страница 10: ...the fiber port receives an RAI signal this will force AIS to transmit on the COAX Line Loopback Testing The iMcV DS3 E3 LineTerm includes two loopback test modes Coax Loopback and Fiber Loopback The following illustrations show the path that a signal takes in each of the loopback test modes Each loopback performs the following Copies the incoming signal back out to the origin while continuing to t...

Страница 11: ...till valid Remote loopback tests isolate problems on the coax run between an iMcV DS3 E3 LineTerm module and the connected device while local loopback tests can isolate problems on the fiber connected to the module The following illustrations show a typical progression of loopback tests i e starting by checking the coax segment at the local side then the fiber segment at the remote side etc ...

Страница 12: ...Sequence S1 6 S1 7 OFF Verify the PRBS LED comes ON at the HOST iMcV DS3 E3 LineTerm module to validate the coax wire connections to the Central Office Verify the PRBS LED comes ON at the REMOTE iMcV DS3 module to validate the coax wire connections at the Customer Premises equipment and the fiber line going to the REMOTE iMcV DS3 E3 LineTerm module The fiber line returning from the remote iMcV DS3...

Страница 13: ... LED is ON at both HOST and REMOTE To test a media converter by itself first make sure you have an appropriate fiber patch cable then follow these steps to test 1 Connect the media converter to the BNC device with a coax cable 2 Loop a single strand of fiber from the transmit port to the receive port of your media converter 3 Verify that you have a valid connection for both the BNC and fiber ports...

Страница 14: ...tions Standards Compliance DS3 E3 STS 1 ANSI T1 102 1993 ANSI T1 107 1995 GR 820 CORE DS3 E3 STS 1 Interface BNC coax 75 5 ohms DS3 44 736 Mbps 20 ppm E3 34 368 Mbps 20 ppm STS 1 51 840 Mbps 20 ppm Power Consumption Typical 0 550 Amps 5 V Operating Temperature 32 to 122 F 0 to 50 C Storage Temperature 0 to 160 F 20 to 70 C Humidity 5 to 95 non condensing 0 to 10 000 ft altitude Dimensions Single S...

Страница 15: ...ears this symbol on product or packaging must not be disposed of with unsorted municipal waste This symbol indicates that the equipment should be disposed of separately from regular household waste It is the consumer s responsibility to dispose of this and all equipment so marked through designated collection facilities appointed by government or local authorities Following these steps through pro...

Страница 16: ...nformation in this document is subject to change without notice IMC Networks assumes no responsibility for any errors that may appear in this document iMcV DS3 E3 LineTerm is a trademark of IMC Networks Other brands or product names may be trademarks and are the property of their respective companies Document Number 50 80400 00 A0 January 2008 ...

Отзывы: