!M@ BLOWER POWER
MIN: 30)%
!T@ FACTORY SET
$RETURN$
!N@ BOILER OFF
TEMP: 35)*
!O@ FEEDER ALARM
TIME: 5)m
!P@ FEEDER ALARM
TEMP:100)*
!R@CH PUMP START
SUMMER: 80)*
!S@KEEPING BOILER
TEMP NO)
M) Blower minimum power.
The blower power lower limit.
N) The temperature limit below which controller makes the boiler OFF when
the
FIRE UP TIME
is completed.
O) The coal pushing time when the feeder alarm temperature is exceeded. (To
prevent the flashback from the boiler to coal container).
P) Feeder alarm temperature value. Exceeding this temperature the feeder
starts its operation to withdraw fire from feeder to the boiler. (To prevent
the flashback from the boiler to coal container).
R) CH pump alarm temperature to start CH pump in SUMMER mode. When
this temperature value is exceeded CH pump starts working to cool down
boiler. (To avoid boiling water in the boiler).
S) Parameter informing if in case of CH pump stop due to obtaining the preset
room temperature value,
i
)
boiler will obtain the preset boiler temperature and keep it (
on
display)
ii)
boiler will be in HOLD status till CH pump start (
NO
on display)
YES
T) Return to the factory settings. Controller makes possible the return to
factory settings. After pressing the question concerning confirmation
of your decision will appear.