Note panels are usually supplied pre-configured so this many not be necessary, check 
shipping documentation

It is recommended to follow the set up sequence below when configuring and installing a control 
panel from new.

Perform a sensor FIND and automatically install detector data.     Engineers Menu .... Find Option

With Sensors and Relays Installed download the panel setup to IGD’s Panel Seup App to configure 
the system. It will be necessary to upload this once completed and re-start the controller for it to take 
effect. 

Perform a Relay FIND

Allow the system to run for at least an hour to allow detectors to fully stabilise to the site conditions.

Should any detectors require re-calibration 

Detectors are supplied pre-calibrated. Follow the Bump Text video on the IGD online Academy to 
check both detector calibration and to prove the system programmed cause and effect. Ensure all 
interfaces to third party devices and systems function as required. Note that individual relays can be 
directly energised and de-energised to aid checking

Ensure there are no indicated system errors in normal operation.

Zero each connected detector.     User Menu ZERO

Calibrate each detector.     User Menu CALibrate

Note IGD calibration and gas adaptor kits are available and necessary to perform calibration and 
bump testing. Record all results for traceability.

find sen

1 of 12

find rly

1 of 12

zero

1 of 15

cal

2 of 15

Putting Into Service

Note that this product should be supplied via a fused spur. Ensure cables used are suitable for both 
their intended area of operation and load capability. This product should only be installed by a 
competent person.

If you are uncertain how to zero/calibrate or locate your gas detectors and system components then 
use IGD’s online training academy.

If your application is safety related you must ensure you are a competent person with demonstrable 
training. If in doubt check with IGD for help and support.

Follow the 2-Wire Installation guide

if you don't have a copy of this download it from www.internationalgasdetectors.com

This provides location as well as cabling/installation guidance.
Failure to observe correct installation can have an adverse affect on system operation 
and performance

To set alarm levels and programme the required cause and effect you will need to 
access the controller using IGD’s Panel Setup App for Android. Download the Panel 
Setup App from the Google Play Store to a suitable blue tooth enabled tablet or 
Phone. Android 4.1.1 or later operating system and min 7” display recommended.

TEST RLY

9 of 12

Содержание TOC-650-150

Страница 1: ...r a t i o n a n d M a i n t e n a n c e V 3 1 Triton House Crosby Street Stockport Sk2 6SH England T el 44 0 161 483 1415 Fax 44 0 161 484 2345 Email sales internationalgasdetectors co uk Website www...

Страница 2: ...10 4 14 5 7 12 23 27 27 Addressable Detector Node Highway Hub Controller Overview Relay Card Overview Relay Card Setup User Actions Overview Menu overview Putting Into Service New Setup Sequence The S...

Страница 3: ...aster Salve Brief Introduction Jog Wheel Interface Service Maintenance The Control Panel leaves the factory configured for the supply voltage stated on the customers order Should the control panel be...

Страница 4: ...0V AC 50 60Hz by selection 1 LEL 2 x 8 LCD Display and Jog Wheel 0 1ppm Full EC Declaration appears on Page 4 0 to 55 Degrees Centigrade IP ratings do not imply that the equipment will detect gas duri...

Страница 5: ...aratus using software and or digital technologies Excluding requirements for SIL EMC Generic standards Immunity for industrial environments Electrical apparatus for the detection and measurement of fl...

Страница 6: ...which supplies gas at 0 5L Min Important Notes Panel Options TOCSIN 750 Series Controller TOCSIN 750 Series Annunciator Options With Display Relay Output Digital or Analogue Input Flammable Gas Detect...

Страница 7: ...tem cables must be screened refer to installers guide General Power can be taken from system modules for small current devices such as LED beacon sounders and is limited to 100mA per module Highways a...

Страница 8: ...this document prior to installation 2 WIRE SYSTEMS 2 W i r e G a s D e t e c t i o n S y s t e m I n s t a l l e r s G u i d e V x x OLIVER IGD Triton House Crosby Street Stockport SK2 6SH England T...

Страница 9: ...upporting 32 Devices 128 Devices in Total Two display options either 650 style with jog wheel or HMI Style touch screen display Note both displays can be tted at the same time which can allow the HMI...

Страница 10: ...DOWN BUTTON UP BUTTON Each Addressable relay card must have its own unique base address This can be set on the card and is indicated below The relays are then addresses numbered from that base address...

Страница 11: ...this one Base Address set up LED s and interface for the relay card In all Cases Relay contact ratings 5A 250V AC Non Inductive 5A 30V DC Non Inductive Spike suppression must be fitted Note that FAULT...

Страница 12: ...nalogue and digital inputs that can be used to read data onto the system from external devices Setup of the inputs type range addressing etc is controlled via IGD s Android Apps Wiring options are ind...

Страница 13: ...put DVM Test Point DVM Test Point Housing Sealing Environment Temperature Voltage Communication Display Analogue I P Sounder Digital Input Relay Pellistor Port Digital Output Comm Port 2 3 4 5 6 7 1 S...

Страница 14: ...threshold it will not be possible to reset the alarm Once fully installed the TOC 650 controller will continuously monitor connected gas detectors and sensors and compare current values with any set a...

Страница 15: ...D Red Continuous on Alarm Level 2 Flashes on Alarm Level 1 Power LED Green Selector Button Selector Jog Wheel WARMUP 600s o Indicate board tested status end user should see PASSED with a green backlig...

Страница 16: ...ement With the correct password displayed press the centre selection button to go to the menu or function Current Channel Reading Inhibit the control panel for up to 60 minutes Use this option if cali...

Страница 17: ...Use this option to FIND Relay Outputs Use to Access Device Diagnostics Set the System Time Set the System Date Move to the USER 100 Menu Use to enable Disable Reset Bluetooth Use to Energise De energ...

Страница 18: ...8 ENG MENU 7 of 8 EXIT 8 of 8 Production Menu Options Provides access for control panel set up and diagnostic functions Use this option to Reset the Hubcard System Re boot Reset Hubcard to defaults Di...

Страница 19: ...Menu CALibrate Note IGD calibration and gas adaptor kits are available and necessary to perform calibration and bump testing Record all results for traceability find sen 1 of 12 find rly 1 of 12 zero...

Страница 20: ...for detectors and I O interface nodes and the relevant check points Warm Up Period In normal operation mode the TOC 650 communicates to each detector or node in turn and displays the data on screen Pr...

Страница 21: ...ed Check the shipping TOC 650 SET UP REPORT to check how the controller and interfacing detectors and nodes have been configured Ensure that the detector addresses match the document and required site...

Страница 22: ...he following manner Press and hold button until prompted to release The system starts discovering connected devices Display indicates devices found so far Display indicates progress When the discovery...

Страница 23: ...ro gas and zero the channel observe and record result Notes All gas detectors will require periodic ZERO and CALIBRATION The calibration interval depends on a number of environmental factors such as t...

Страница 24: ...e is no gas present by using a portable detector B Use a suitable ZERO gas as follows Zero gas should have a humidity between 0 90 RH O2 CO2 NITROGEN PELLISTOR INSTRUMENT AIR TOXIC GASES NITROGEN The...

Страница 25: ...erate This type of alarm is typically used in safety applications for Oxygen deficiency monitoring where you are monitoring for a falling Oxygen level Press and hold until prompted to release to selec...

Страница 26: ...t a zero or calibration the controller sends the request to the detector head for action and monitors the result This means that detectors can be supplied pre calibrated The reading is now displayed s...

Страница 27: ...Calibrate zero point Standard accessories Supplied 1 x Terminator Set 5 off 1 x Diode Pack 1 x Snubber 1 x Resistor Pack Battery Care Installation The batteries will come pre installed but will be di...

Страница 28: ...ter Disk 5110101 Remote Gassing Port 5134601 40mm Stop Button 5138601 Collector Cone Ring Lock 5138701 T103 Splash Guard 5138801 Collector cone kit MK6 TOC GLAND M20 Snap fit cable glad 5925801 Univer...

Отзывы: