37
Panel Beacon Sounder Output
Panel Displays
The 750 hub card is fitted with two SSR outputs intended for use with Beacon Sounders.
During a FIND command these will appear on cable 0 (internal to the hub card) and can be
assigned to alarm levels during the alarm setup routine. Addresses will be assigned as 105
and 106 during the FIND operation.
Output Drive 24V DC
@ 100mA
The 750 Hub Card also
incorporates a built in
sounder. This also has its
own address and will appear
by default as relay O/P 107
after a FIND operation.
Two display option are available. A 2 x 8 RGB LCD, supplied as standard on the 650 model and a
colour HMI touchscreen supplied as standard on the 750 model. Both run from different ports on
the same hub card.
TOC-650 Style display connects
using a ribbon cable interface
and must be local to the hub PCB
TOC-750 Style display connects through an
RS485 Interface which allows the display to be
remote from the hub if required
Note the hub PCB can run either
display, both together with the
HMI display remote or the hub
can run ‘blind’ with no connected
display.
1 2
3 4
IN+ OUT+
Beacon
Sounder
Sounder is Address 105
Beacon is Address 106