36
Panel Inputs 1 and 2 Cable 0
Alarm and Fault Relays
The 750 hub card is fitted with two digital inputs for use when interfacing to volt free contacts.
These can be used for example with slam switches or a relay output from another system
such as a fire alarm panel. They appear during a FIND command on cable 0 (internal to the
hub card) and will have input addresses 1 and 2 assigned by default. Alarms can be set
against these two channels in the same manner as any other detector. Note these channels
are supplied linked out and will always be the first two channels on the control panel.
switched inputs 1 and 2, volt free contacts
Normally Closed Loops Opening on Alarm
0V DC
24V DC
A1
A2
Example fit protection diodes when switching
external DC loads. 1N4004 Diodes are provided
with each module.
For Additional Diode Packs
IGD PN: TOC-750-DIO
Fault
101
Relay
102
Relay
103
Relay
104
All Relay
NO COM NC
COMM
Normally Open
FOR DC LOADS
DO NOT EXCEED
30V DC 5A
The four relays included on the hub
card can be assigned to alarm levels
in the relay alarm routine. They
appear on internal cable 0 during a
relay FIND.
All 4 relays are normally energised,
de-energising on alarm or on loss of
power to panel
Slam Switches
Address = 1
Key Switches
Address = 2
Note these inputs typically used for call
points / input from Fire Systems etc
Содержание 2-Wire Systems
Страница 4: ...3 SECTION 1 MOUNTING DETAILS FOR EQUIPMENT...
Страница 9: ...8 SECTION 2 SITING GAS DETECTORS...
Страница 16: ...15 SECTION 3 GENERAL CABLING PRINCIPLES CABLE TYPES AND CABLE SIZING...
Страница 23: ...22 SECTION 4 MAKING DEVICE CONNECTIONS TO DETECTOR NODES...
Страница 35: ...34 SECTION 4 Control Panel Interfaces and Connections...
Страница 51: ...50 Notes...