► To prevent negative effects on the functions caused by noise voltages, lay
sensor cables and load cables separately� Maximum length of the sensor cable:
250 m�
► Use a screened sensor cable�
The outputs are short-circuit proof and can be configured as either normally closed
or normally open�
In addition an analogue signal can be provided on output [OU 1] (0/4���20 mA) (e�g�
acceleration values)�
7.1 Wiring
18
17
20
19
14
13
16
15
22
21
24
23
6
5
8
7
2
1
4
3
10
9
12
11
Supply L- (GND)
OU 1: switch/analog
OU 2: switch
IN 1 (0/4...20 mA / pulse)
GND 1
IN 2 (0/4...20 mA / pulse)
GND 2
1
2
3
4
4
3
2
1
1
2
3
4
1
2
3
4
Supply L+ (24 V DC ±20 %)
Sensor 1
Sensor 2
Sensor 3
Sensor 4
Wiring of the sensors 1���4 (S1���S4) according to the connected unit
Sensor
VSA
IEPE/VSP
0���20 mA
S1
S2
S3
S4
09
16
20
24
BN: L+ (+ 9 V)
not connected
(n�c�)
not connected
(n�c�)
10
15
19
23
WH: signal
IEPE +
signal
11
14
18
22
BU: GND
IEPE -
GND
12
13
17
21
BK: Test
not connected
(n�c�)
not connected
(n�c�)