9  Operation

 

Check the safe functioning of the unit�

 Display by LEDs:

LED AS-i green lights

AS-i voltage supply OK

LED AUX green lights

External voltage supply 24 V OK

LEDs O1���O4 yellow light

Analogue signal within the measuring range or no 

actuator connected� It cannot be detected whether 

a 0 V signal is applied or whether no actuator is 

connected�

LEDs O1���O4 yellow flash

Analogue signal outside the measuring range 

(overflow)

LED FAULT red lights

Peripheral fault 

A peripheral fault is indicated if at least one of the 

analogue signals is outside the value range�

LED yellow DIAG

 -DIAG lights

 -DIAG flashes

 -DIAG off

Internal diagnostics

 -no fault

 -internal fault (replace module)

 -internal fault (replace module)

10  Maintenance, repair, disposal

10.1  Maintenance

The unit is maintenance-free�

10.2  Cleaning of the housing surface

 

Disconnect the device�

 

Clean the device from dirt using a soft, chemically untreated and dry cloth�

Micro-fibre cloths without chemical additives are recommended�

10.3  Repair

 

The device must only be repaired by the manufacturer�

10.4  Disposal

 

Dispose of the device in accordance with the national environmental 

regulations�

Содержание SmartLine AC3218

Страница 1: ...Operating instructions AS i SmartLine module AC3218 AC3219 80255917 00 01 2017 UK...

Страница 2: ...on of an actuator with intrinsic supply 7 6 2 3 Connection of an actuator with separate 24 V supply 8 6 2 4 Electrical connection 0 V terminal 8 6 3 Connection analogue module AC3219 0 10 V 9 6 3 1 Co...

Страница 3: ...or the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features If the operating instructions or the techni...

Страница 4: ...3218 Rmin for voltage output 1 k AC3219 AS i profile S 7 3 6 Maximum number of modules per AS i system 31 Conversion time digital analogue in the slave with four channels 1 ms Actuator supply from AS...

Страница 5: ...ace between the unit and the top and bottom of the control cabinet to enable air circulation and to avoid excessive heating Take into account the internal heating of all devices when mounting several...

Страница 6: ...stallation of electrical equipment must be adhered to Disconnect power Connect the unit 6 1 Wiring O actuator supply 24 V C1 C4 analogue output current AC3218 V1 V4 analogue output voltage AC3219 O ac...

Страница 7: ...and O are not used with actuators without separate voltage supply 1 Analogue module 2 Actuator without separate supply 6 2 2 Connection of an actuator with intrinsic supply O C1 C4 0 V O A 2 wire actu...

Страница 8: ...not connect the 0 V terminals analogue output 0 V of the respective channels of the current output modules to each other This connection leads to faulty current signals The connection of the 0 V term...

Страница 9: ...3 Connection analogue module AC3219 0 10 V 6 3 1 Connection of an actuator with intrinsic supply O V1 V4 0 V O An actuator with intrinsic supply e g a voltmeter is connected via the terminals V1 4 and...

Страница 10: ...be taken from the terminals V1 V4 and 0 V The terminals O and 0 V must be con nected to each other via a link 1 Analogue module 2 Actuator with separate supply 7 Parameter setting Parameter bit Desig...

Страница 11: ...711 2CEC on above nominal range 11 5 V 11500 2CEC flashing overflow 8 3 Transmission time of the analogue values The transmission time of the analogue values depends on the conversion time of the digi...

Страница 12: ...eripheral fault is indicated if at least one of the analogue signals is outside the value range LED yellow DIAG DIAG lights DIAG flashes DIAG off Internal diagnostics no fault internal fault replace m...

Страница 13: ...13 UK 11 Scale drawing 108 25 4 93 126 LED 35...

Отзывы: