39
UK
10.5.6 Measured value damping
► Select [dAP] and set the damping constant in seconds (τ value 63 %).
Menu CFG:
[dAP]
10.5.7 Error behaviour of the outputs
►
Select [FOU1] and set the value:
1� Switching output:
-On = Output 1 switches ON in case of a fault�
-OFF = Output 1 switches OFF in case of an error�
-OU = Output 1 switches irrespective of the fault as defined with the
parameters�
2� Frequency output:
-On = 130% of FrEP�
-OFF = 0 Hz
-OU = continues running
►
Select [FOU2] and set the value:
1� Switching output:
-On = Output 2 switches ON in case of a fault�
-OFF = Output 2 switches OFF in case of a fault�
-OU = Output 2 switches irrespective of the fault as defined with the
parameters�
2� Analogue output:
-On = The analogue signal goes to the upper fault value
�
-OFF = The analogue value goes to the lower fault value
-OU = The analogue signal corresponds to the measured value�
Menu CFG:
[FOU1]
[FOU2]
10.5.8 Activating / deactivating empty pipe detection
►
Select [OU1] or [OU2] and set dOU�
►
Select [EP�On] and set the function:
-OFF = empty pipe detection deactivated�
-On = empty pipe detection activated�
Main menu:
[OU1]
[OU2]
Menu EPD:
[EP�On]
10.5.9 Empty pipe detection switching logic
►
Select [P-n] and set PnP or nPn�
Menu CFG:
[P-n]