32
9 Set-up
After power up and expiry of the start up delay time (approx� 5 s) the unit is in the
RUN mode (= normal operating mode)� It carries out its measurement and evalua-
tion functions and generates output signals according to the set parameters�
• During the start up delay time the outputs are switched as programmed:
-ON with normally open function (Hno / Fno)
-OFF with normally closed function (Hnc / Fnc)�
• If output 2 is configured as analogue output, the output signal is at 20 mA (cur-
rent output) or 10 V (voltage output) during the start up delay time�
10 Parameter setting
Parameters can be set before installation and set-up of the unit or during opera-
tion�
If you change parameters during operation, this will influence the function
of the plant�
►
Ensure that there will be no malfunctions in your plant�
During parameter setting the unit remains in the operating mode� It continues to
monitor with the existing parameter until the parameter setting has been complet-
ed�
The parameters can also be set via the IO-Link interface
�
CAUTION
If the medium temperature is above 50 °C (122 °F) parts of the housing can
increase in temperature to over 65 °C (149 °F)�
►
Do not press the pushbuttons manually� Instead use another object (e�g�
ballpoint pen)�