39
UK
10.4.2 Limit monitoring OUT1 or OUT2 / window function
►
Select [uni�T] and set the unit of measurement�
►
Select [SELx] and set TEMP�
►
Select [oux] and adjust the switching signal:
-Fno = window function / normally open
-Fnc = window function / normally closed
►
Select [FHx] and set the upper limit of the window section�
►
Select [FLx] and set the lower limit of the window sector�
Menu OUTx:
[SELx]
[oux]
[FHx]
[FLx]
10.4.3 Analogue signal temperature OUT2
►
Select [uni�T] and set the unit of measurement�
►
Select [SEL2] and set TEMP�
► Select [ou2] and select analogue signal: I (4...20 mA)
►
Select [ASP2] and set the value at which 4 mA is provided�
►
Select [AEP2] and set the value at which 20 mA is provided�
Menu OUT2:
[SEL2]
[ou2]
[ASP2]
[AEP2]
10.5 Settings for pressure monitoring
10.5.1 Limit monitoring OUT1 or OUT2 / hysteresis function
►
Select [uni�P] and set the unit of measurement�
►
Select [SELx] and set PRES�
►
Select [oux] and adjust the switching signal:
-Hno = hysteresis function / normally open
-Hnc = hysteresis function / normally closed
►
Select [SPx] and set the value at which the output is set�
►
Select [rPx] and set the value at which the output is reset�
Menu OUTx:
[SELx]
[oux]
[SPx]
[rPx]
10.5.2 Limit monitoring OUT1 or OUT2 / window function
►
Select [uni�P] and set the unit of measurement�
►
Select [SELx] and set PRES�
►
Select [oux] and adjust the switching signal:
-Fno = window function / normally open
-Fnc = window function / normally closed
►
Select [FHx] and set the upper limit of the window section�
►
Select [FLx] and set the lower limit of the window sector�
Menu OUTx:
[SELx]
[oux]
[FHx]
[FLx]