38
10.3.3 Manual counter reset
►
Select [rTo] and set rES�T�
> The totaliser is reset to zero�
Menu EF:
[rTo]
10.3.4 Time-controlled counter reset
►
Select [rTo] and set the requested value (intervals of hours, days or
weeks)�
> The totaliser is reset automatically with the value now set�
Menu EF:
[rTo]
10.3.5 Deactivation of the counter reset
►
Select [rTo] and set OFF�
> The totaliser is only reset after overflow�
Menu EF:
[rTo]
10.3.6 Counter reset using an external signal
► Select [ou2] and set In.D.
►
Select [DIn2] and set counter reset signal:
-HIGH = reset for high signal
-LOW = reset for low signal
-+EDG = reset for rising edge
-–EDG = reset for falling edge
> The totaliser is reset to zero�
Menu OUT2:
[ou2]
[DIn2]
10.4 Settings for temperature monitoring
10.4.1 Limit monitoring OUT1 or OUT2 / hysteresis function
►
Select [uni�T] and set the unit of measurement�
►
Select [SELx] and set TEMP�
►
Select [oux] and adjust the switching signal:
-Hno = hysteresis function / normally open
-Hnc = hysteresis function / normally closed
►
Select [SPx] and set the value at which the output is set�
►
Select [rPx] and set the value at which the output is reset�
Menu OUTx:
[SELx]
[oux]
[SPx]
[rPx]