4.2 Select medium (MEdI)
The unit has characteristic curves for different media� Depending on the operating
mode, the following media can be selected in the menu
Operating mode
Medium
REL LIQU GAS
*OIL1:
Viscosity ≥ 40 mm²/s at 40 °C / ≥ 40 cSt at 104 °F
**OIL2:
Viscosity ≤ 40 mm²/s at 40 °C / ≤ 40 cSt at 104 °F
H2O
x
x
OIL1*
x
x
OIL2**
x
x
GLYC
x
x
AIR
x
x
4.3 Define the internal pipe diameter (diA)
In the operating modes LIQU and GAS the internal pipe diameter has to be en-
tered to define the volumetric flow
�
4.4 Customer-specific calibration (CGA)
Via the calibration factor CGA the sensor can be adjusted to a reference flow in
the application�
The customer-specific calibration allows changing the gradient of the curve of
measured values� It influences the display and the outputs�
140 % MEW
100 % MEW
60 % MEW
MEW
Q
A
V1
V0
V2
A = Operating value for display and
output signals
Q = Flow
MEW = Final value of the measuring
range
V0 = Curve of measured values at
factory setting
V1, V2 = Curve of measured values after
calibration