22
10.3 Settings for temperature monitoring
10.3.1 Analogue output for temperature (OUT1)
►
Select [ASP1] and set the temperature value at which the output signal
is 4 mA�
►
Select [AEP1] and set the temperature value at which the output signal
is 20 mA�
Main menu:
[ASP1]
[AEP1]
10.4 User settings (optional)
10.4.1 Configure standard display
►
Select [SELd] and determine the standard unit of measurement:
-FLOW = current flow in the standard unit of measurement is displayed�
-
TEMP = current medium temperature in °C (SAxx14: °F) is displayed.
►
Select [diS] and set the update rate and orientation of the display:
-d1, d2, d3: update of the measured values every 50, 200, 600 ms�
-
rd1, rd2, rd3: display as for d1, d2, d3; rotated by 180°.
-OFF = measured value display is deactivated in the RUN mode�
The LEDs remain active even if the display is deactivated� Error
messages are displayed even if the display is deactivated�
Menu DIS:
[SELd]
[diS]
10.4.2 Set the standard unit of measurement for flow
►
Select [uni] and set the unit of measurement:
SAxx04: l/min, m
3
/h, m/s
SAxx14: cfm, gpm, fps
[uni] is only available if the operating mode GAS or LIQU is selected�
For the operating mode REL the flow value is always displayed in %
of the measuring range�
Menu CFG:
[uni]
10.4.3 Select the medium
►
Select [MEdI] and define the medium to be monitored:
H2O, OIL1*, OIL2**, GLYC, AIR�
Depending on the operating mode different media are available
4�2)�
*OIL1 = high-viscosity oil (≥ 40 mm²/s at 40 °C / ≥ 40 cSt at 104 °F)
**OIL2 = low-viscosity oil (≤ 40 mm²/s at 40 °C / ≤ 40 cSt at 104 °F)
Menu INI:
[MEdI]