9.3 User settings (optional)
9.3.1 Set delay for the switching outputs
• [dS1] = time delay for SP1 / FH1� If the system pressure exceeds SP1 or
if the system pressure enters the acceptable range (window), the output
changes the switching status when the time dS1 has elapsed�
• [dr1] = time delay for rP1 / FL1� If the system pressure falls below rP1 or
if the system pressure leaves the acceptable range (window), the output
changes the switching status when the time dr1 has elapsed�
►
Select [dS1] or [dr1] and set the value between 0 and 5000 ms in steps
of 2 ms (at 0 the time delay is not active)�
9.3.2 Set damping for the switching outputs
►
Select [dAP] and set the value�
dAP value = response time between pressure change and change of the
switching status in milliseconds�
The following fixed values can be set; they define the switching frequency (f
in Hz) of the output:
dAP 6
10
30
60 100 250 500 1000 2000
f
80
50
16
8
5
2
1
0�5
0�25
9.3.3 Configuration of the display
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms�
-[d2]: update of the measured values every 200 ms�
-[d3]: update of the measured values every 600 ms�
-[Ph]: display of the pressure peaks remains for a short time (peak
hold)�
-[rd1], [rd2], [rd3], [rPh]: display as for d1, d2, d3; rotated by 180°�
-[OFF]: the display is switched off in the operating mode�
►
Select [cLor] and define the colour of the digital display:
-[r-on]: display = red if output 1 is switched; display = green if output 1
is not switched�
-[G-on]: display = green if output 1 is switched; display = red if output 1
is not switched�
-[red]: the colour of the display is red / does not change�
-[Gren]: the colour of the display is green / does not change�