4.2 Switching function

OUT1 changes its switching state if it is above or below the set switching limits 

(SP1, rP1) The following switching functions can be selected:
• 

Hysteresis function / normally open: [OU1] = [Hno] (→ fig. 1).

• 

Hysteresis function / normally closed: [OU1] = [Hnc] (→ fig. 1).

First the set point (SP1) is set, then the reset point (rP1) with the requested 

difference
• 

Window function / normally open: [OU1] = [Fno] (→ fig. 2).

• 

Window function / normally closed: [OU1] = [Fnc] (→ fig. 2).

The width of the window can be set by means of the difference between SP1 and 

rP1 SP1 = upper value, rP1 = lower value



1

2

P = system pressure; HY = hysteresis; FE = window

4.3 Analogue function

The analogue output can be configured

[OU2] defines whether the measuring range is provided as 420 mA ([OU2] = [I]), 

or 010 V ([OU2] = [U]) Analogue measuring range for PN004A = 010 bar

Содержание PN00 A Series

Страница 1: ...Operating instructions Pressure sensor PN00xA 704531 00 01 2019 UK...

Страница 2: ...Parameter setting 10 9 1 General parameter setting 10 9 2 Configuration of the display optional 12 9 3 Configuration of output 1 12 9 3 1 Setting of the output function 12 9 3 2 Setting of the switch...

Страница 3: ...erty can occur Check the compatibility of the product materials chapter 12 Technical data with the media to be measured in all applications Observe the instructions for the safe use in hazardous areas...

Страница 4: ...kPa bar 100 Analogue measuring range for PN004A 0 10 bar Avoid static and dynamic overpressure exceeding the given overload pressure by taking appropriate measures The indicated bursting pressure must...

Страница 5: ...then the reset point rP1 with the requested difference Window function normally open OU1 Fno fig 2 Window function normally closed OU1 Fnc fig 2 The width of the window can be set by means of the dif...

Страница 6: ...electrical equipment must be adhered to Voltage supply to EN 50178 SELV PELV For the scope of validity cULus The unit shall be supplied from an isolating source and protected by an overcurrent device...

Страница 7: ...ent LEDs 5 to 7 not used LED 8 switching status OUT1 lights if output 1 is switched 9 Alphanumeric display 4 digits Indication of the current system pressure Indication of the parameters and parameter...

Страница 8: ...8 8 Menu 8 1 Menu structure...

Страница 9: ...r normally closed nc OU2 Output function for OUT2 Analogue signal for the current system pressure 4 20 mA I or 0 10 V U EF Extended functions opening of menu level 2 Uni Standard unit of measurement f...

Страница 10: ...r flashes for 5 s After 5 s Setting value is changed incrementally by pressing the button once or continuously by keeping the button pressed Numerical values are incremented continuously To reduce the...

Страница 11: ...t parameter of the sub menu is displayed here Uni Locking unlocking The unit can be locked electronically to prevent unintentional settings Make sure that the unit is in the normal operating mode Pres...

Страница 12: ...ation of output 1 9 3 1 Setting of the output function Select OU1 and set the function Hno hysteresis function normally open Hnc hysteresis function normally closed Fno window function normally open F...

Страница 13: ...sure change and change of the switching status in milliseconds The value for dAP defines the switching frequency f of the output the following fixed values can be set dAP 3 6 10 17 30 60 125 250 500 f...

Страница 14: ...Mode Enter until the requested parameter is displayed Press Set briefly The unit displays the corresponding parameter value for about 15 s After another 15 s the unit returns to the Run mode 10 2 Fau...

Страница 15: ...6 DC1 Current consumption mA 50 Current rating per switching output mA 250 Protected against reverse polarity and overload up to 40 V Short circuit protection integrated watchdog Voltage drop V 2 Powe...

Страница 16: ...steel 316 L PC Makrolon PBT Pocan PEI FPM Viton Protection IP 65 III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 10 2000 Hz Switching cycles min 100 million Op...

Страница 17: ...14 4 0 1 0 1 kPa 99 0 0 0 99 5 0 5 0 5 inHg 29 2 0 0 29 3 0 2 0 1 P increments 13 Factory setting Factory setting User setting SP1 25 VMR rP1 23 VMR OU1 Hno OU2 I dS1 0 0 dr1 0 0 dAP 6 diS d2 Uni bAr...