21
UK
For 2-wire operation those menu items referring to switching functions are
not active ( 8 Menu structure); in addition, those parameter values of some
menu items referring to switching functions cannot be selected.
• If [SLoc] is displayed when attempting a modification of a parameter value,
the sensor is locked by the software. This locking can only be removed with a
parameter setting software.
• When parameter setting is done with the user interface of the ifm Container
program, the values can be directly entered in the specified fields.
•
For IO-Link parameter setting → device-specific parameter lists at:
www.ifm.com
• Change from menu level 1 to menu level 2:
►
Press [Mode/Enter] until [EF] is
displayed.
►
Briefly press [Set].
> The first parameter of the submenu is
displayed (here: [Uni]).
If menu level 2 is protected by an access
code, "Cod1" flashes in the display.
►
Press and hold [Set] until the valid
code no. is displayed.
►
Briefly press [Mode/Enter].
When delivered by ifm electronic: no
access restriction.
• Locking / unlocking
The unit can be locked electronically to prevent unintentional settings.
►
Make sure that the unit is in the
normal operating mode.
►
Press [Mode/Enter] + [Set] for 10 s.
> [Loc] is displayed.
During operation: [Loc] is briefly displayed if you try to change parameter values.
For unlocking:
►
Press [Mode/Enter] + [Set] for 10 s.
> [uLoc] is displayed.