Install the photoelectric safety sensor at a distance 

that is greater or equal to the minimum safety 

distance (S) so that the hazardous area (A) can 

only be accessed after complete standstill of the 

hazardous machine motion� 

According to the European Standard EN 999:2008 the 

following formula is to be used to calculate the minimum 

safety distance (S):

S = K (t1 + t2) + C

C = 8 (d - 14)

A = hazardous area

H = protected area height

S = min� safety distance

C = additional distance

S

Minimum safety distance

mm

K

Speed of approach of the object towards the hazardous area

mm/s

t

1

Total response time of the protective equipment, from release to switching off s

t

2

Total response time of the machine, from the stop signal to switching off or to 

passing into the state defined as safe

s

C

Additional distance

mm

d

Resolution (detection capability)

mm

Non-compliance with the minimum safety distance may lead to restrictions 

to or loss of the safety function�

Application example:

A = hazardous area

S = min� safety distance

Содержание OY Series

Страница 1: ...704701 02 12 2018 Original operating instructions Photoelectric safety sensors safety light curtain for finger protection resolution detection capacity 14 mm OY UK...

Страница 2: ...y light curtains resolution 14 mm 12 6 4 Fixing and optical alignment 13 6 4 1 Optical alignment 14 6 5 Distance of the reflecting surfaces 15 6 6 Multiple systems 17 6 7 Use of corner mirrors 18 7 El...

Страница 3: ...ety light curtains 26 11 Scale drawing 27 12 Technical data 28 12 1 Safety light curtains 14 mm resolution 29 13 Troubleshooting 29 13 1 Fault diagnosis transmitter 29 13 2 Fault diagnosis receiver 30...

Страница 4: ...ions before use to familiarise yourself with operating conditions installation and operation Adhere to the safety instructions 1 1 Symbols used Instruction Reaction result Cross reference LED off LED...

Страница 5: ...it externally before handling it Disconnect all relay load circuits that are supplied independently After setup the system has to be subjected to a complete function check Only use the unit under the...

Страница 6: ...electric safety sensors with the chemicals used Adhere to the principle of normally closed operation for all external safety circuits connected to the system If the photoelectric safety sensors go int...

Страница 7: ...d suitable nuts 1 copy operating instructions photoelectric safety sensors reference no 704701 If one of the above mentioned components is missing or damaged please contact one of the ifm branch offic...

Страница 8: ...between transmitter and receiver 12 Technical data If the protected are is clear the two outputs OSSDs of the receiver are active If an object O with a diameter greater than or equal to the resolution...

Страница 9: ...hazardous area can only be accessed via the protected area Depending on the application other mechanical protective equipment may be necessary The operating conditions at the mounting location must no...

Страница 10: ...allation Wrong installation 6 2 Calculation of the minimum safety distance There must be minimum safety distance between the photoelectric safety sensor and the point of danger This distance must be e...

Страница 11: ...rotected area height S min safety distance C additional distance S Minimum safety distance mm K Speed of approach of the object towards the hazardous area mm s t1 Total response time of the protective...

Страница 12: ...14 This formula applies to minimum safety distances S between 100 and 500 mm The min safety distance S must be 100 mm A hazardous area H height S min safety distance G reference level If due to the s...

Страница 13: ...he supplied mounting accessories so that they are exactly opposite each other Align the transmitter and the receiver so that they are in parallel at the same height and the plugs face the same directi...

Страница 14: ...afety sensors Description Receiver 2 colour LED 2 colour LED red green yellow blue Receiver does not detect any light beams Receiver detects some light beams Receiver detects all light beams with a we...

Страница 15: ...een reflective surfaces and the protected area P must be observed In case of non respect an object to be detected may not be detected In case of improper handling of the product the safety and physica...

Страница 16: ...16 Minimum distance to reflective surfaces D minimum distance in mm I protected area width range m...

Страница 17: ...stem can only be detected by the respective receiver The following important rules for installation are to be observed to avoid mutual interference of several systems Arrangement A Arrangement B R1 T1...

Страница 18: ...here U shaped access protection is implemented using two mirrors receiver R transmitter T A hazardous area M corner mirror S min safety distance Dx side length Install the mirrors so that the minimum...

Страница 19: ...t Pin Name Type Description 4 2 1 3 5 1 L 24 V DC Input Operating voltage 2 Range 0 Configuration protected area width 3 L 0 V DC Operating voltage 4 Range 1 Configuration protected area width 5 FE Fu...

Страница 20: ...External feedback contact 5 SEL_A Input Operating mode Safety light curtains 6 SEL_B Input 7 0 V DC Operating voltage 0 V DC 8 FE Functional earth For information about available sockets connectors s...

Страница 21: ...to L 0 V DC 6 4 8 5 L L B Automatic with monitoring K1_K2 K1_K2 restart Connects to L 24 V DC via NC contacts of K1_K2 SEL_A Connects to L 24 V DC SEL_B Connects to L 0 V DC 6 4 8 5 L L C Manual K1_K...

Страница 22: ...d persons can be present in the hazardous area after accessing the protected area without being detected The start restart button has to be outside the hazardous area It has to be installed so that th...

Страница 23: ...tested by a process control system or a control module 7 1 Table Configuration protected area width The test pulse interrupts the light emission by the transmitter and the outputs carry a 0 signal 10...

Страница 24: ...activated The green LED flashes twice when the system is switched on if the unit has been configured with a high range 10 Operation 10 1 Switching state of the outputs The safety light curtains have...

Страница 25: ...ed state In switched state the receiver provides a current of 24 V DC logic 1 to both outputs Output characteristics The output characteristics follow the characteristics of the input according to IEC...

Страница 26: ...on about available test rods see www ifm com Products Accessories Let the test object enter the protected area and move it slightly downwards First of all in the centre and then close to the transmitt...

Страница 27: ...0 10 5 28 28 5 5 40 10 20 10 1 5 M5 14 5 30 28 T M12x1 11 29 5 61 5 L R T R L transmitter receiver total length 1 LED 3 colours red green orange 2 LED 2 colours yellow blue 3 LED 2 colours red green a...

Страница 28: ...4 V Max capacitive load CL_max F 0 82 Power on delay time s 2 Mission time TM h 175200 EMC IEC 61496 1 Vibration IEC 61496 1 Shock IEC 61496 1 Ambient temperature C 10 55 Max perm relative air humidit...

Страница 29: ...08 3 7 08 Test pulse duration ti s 80 80 80 80 80 80 80 80 80 80 100 Test pulse interval T ms 3 9 5 7 7 5 9 3 11 1 12 9 14 7 16 5 18 3 20 1 23 7 Ratio ti T 2 1 1 4 1 1 0 9 0 7 0 6 0 5 0 5 0 4 0 4 0 4...

Страница 30: ...g transmitter from high to low Exchange position of transmitter and receiver Change location of the interfering transmitter so that the receiver is not influenced Screen the beams coming from the inte...

Страница 31: ...larly dusty environments we recommend to spray the cleaned front pane with an antistatic product Do not use any aggressive or abrasion developing cleaning agents since they could attack the surfaces T...

Страница 32: ...MTTFd Mean Time To Dangerous Failure OSSD Output Signal Switch Device Output signal switch element static safety related output PFH PFHD Probability of dangerous Failure per Hour PL Performance Level...

Страница 33: ...the stop or shutdown delay of the machine been measured and adapted according to the installation of the safety light curtains 5 Have the safety light curtains been duly fixed and secured against loos...

Отзывы: