7  Operating and display elements

2

1

LED 5

LED 1

LED PWR
LED 4

LED 3

LED 5

1:  Window for optical position indication (OPEN)
2:  Inductive teach button

LED 1 yellow on

switching status OUT1 – valve position open 

LED 2 PWR green on

voltage applied to the unit

LED 3

not used

LED 4 white on

switching status OUT2 - valve position closed

LED 5 (ring)

yellow on - switching status OUT1 
blue on - switching status OUT2
(colours programmable, yellow and blue preset at the 
factory)
red flashing - fault in the unit
• no pulse pick-up available
• teach error - switch points SSC1 and SSC2 overlap
• end position not reached after set time has elapsed
• unit faulty

The LED colours in the table are the default colours and can be customised.

8  IO-Link

This unit has an IO-Link communication interface which enables direct access to 
process and diagnostic data. In addition it is possible to set the parameters of the 
unit while it is in operation. Operation of the unit via an IO-Link interface requires 
an IO-Link master.
With a PC, suitable IO-Link software and an IO-Link adapter cable communication 
is possible when the system is not in operation.

Содержание MVQ101

Страница 1: ...Device manual Valve sensor MVQ101 80270936 00 04 2018 UK...

Страница 2: ...y may occur The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator Installation electrical connection set up opera...

Страница 3: ...h the standard EN 61000 6 4 The unit may cause radio interference in domestic areas The user must take appropriate measures to avoid this interference if necessary 1 2 3 1 Use the two notches at the b...

Страница 4: ...pin 4 Communication IO Link Switching output valve position open in SIO mode OUT 2 pin 2 Switching output valve position closed OUT 3 pin 5 Programmable Switching output valve position open Switching...

Страница 5: ...ctory red flashing fault in the unit no pulse pick up available teach error switch points SSC1 and SSC2 overlap end position not reached after set time has elapsed unit faulty The LED colours in the t...

Страница 6: ...ble Reading current process values Reading changing and saving current parameter settings and transmitting them to other units of the same type Connect the unit via the IO Link interface to a PC or PL...

Страница 7: ...lerance and hysteresis can be set separately for each switch point with an additional seal monitoring for SSC2 9 3 2 Parameter setting via inductive teach button The sensor is adjusted using a metal o...

Страница 8: ...ch button approx 20 s until the LED ring briefly flashes once 10 Settings 2 2 1 Settings tolerance Set a tolerance range between 0 1 and 15 around the taught set switch point 1 Teach point 2 Tolerance...

Страница 9: ...Tolerance width 10 1 Timeout Timeout indicates the maximum duration for closing or opening before the sensor signals a blockage Adjustable time between 0 1 30 s factory setting 30 s In parallel the p...

Страница 10: ...Defect of the unit Puck not used Limit value for the timeout exceeded 10 4 Opening closing duration The minimum maximum closing opening duration of the drive can be freely set and monitored The sensor...

Отзывы: