Binary level sensor

LMT0xA

15

7.7 Unit locking / data storage

The IO-Link master stores all parameters of the connected sensor (data storage) if configured in the
master. When a sensor is replaced by a sensor of the same type, the parameters of the old sensor are
automatically written to the new sensor if configured in the master and if the sensor allows this. For
safety reasons the data storage can be refused by the sensor. Factory setting: [Open]

Data storage

– [Open] = Unit allows parameter download from the master.
– [Locked] = Unit refuses parameter download from the master.

7.8 Full adjustment via IO-Link

Full adjustment enables optimum sensitivity of the unit to be set to the medium to be detected (build-
up and foam are suppressed):

u

Fill the tank/pipe.

u

The probe tip must be completely covered with the medium.

u

Execute the system command [tSP1] or [tSP2].

w

The unit automatically sets the switching thresholds [SPx]/[rPx].

u

Check the function by an application test.

7.9 Parameter setting via the teach input

The teach input must be activated.

u

This requires previous configuration via IO-Link: parameter [ou2] = [tch].

Output OUT2 must be configured as hysteresis function (Hnc or Hno). If the window function is
set, an error during teaching results (

Ò

 Error during teaching).

Only output OUT2 is available in the teach mode. In the teach mode the LEDs indicate the
switching status of output OUT2.

7.9.1 Full adjustment via the teach input

u

Fill the tank until the probe tip is completely covered.

u

Apply Ub+ to pin 4 for > 2 ... < 5 s.

The tool which is available for this process is the teach button (accessory).

w

LEDs flashing at 2 Hz.

w

After teaching the LEDs are on for 2 s. Then the colours change to regular operating mode.

7.9.2 Changing the output function

Output OUT2 can be changed from "NC" (Hnc) to "NO" (Hno) and vice versa.

u

Apply Ub+ to pin 4 for > 5 ... < 10 s.

w

LEDs are flashing, first with 2 Hz, after 5 s with a 1 Hz double flashing.

w

After the change the LEDs are on for 2 s. Then the colours change to regular operating mode.

w

After the successful change, the LEDs are on as follows:

No medium detected

LEDs = yellow (for Hnc)

LEDs = green (for Hno)

Medium detected

LEDs = green (for Hnc)

LEDs = yellow (for Hno)

GB

Содержание LMT0 A Series

Страница 1: ...Operating instructions Binary level sensor LMT0xA 80301827 00 03 2021 GB...

Страница 2: ...9 5 5 1 Installation LMT01A hygiene compliant 10 5 5 2 Installation LMT03A and LMT04A 10 6 Electrical connection 12 7 Parameter setting 13 7 1 IO Link communication interface 13 7 2 Parameter setting...

Страница 3: ...unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfun...

Страница 4: ...the EU directive 94 9 EC annex VIII ATEX group II equipment category 3D 3G If no operating instructions Ex protection related part or EC declaration of conformity are supplied with this product in th...

Страница 5: ...253 mm G1 2 1 Sensitivity adjustable Parameter setting 2 Probe length measured from conical sealing edge Technical data 3 2 Restriction of the application area Not suitable for abrasive media e g quar...

Страница 6: ...tip generates an electrical field that is influenced by the level The nature of the medium as well as build up or foam have different electrical properties that are used for the evaluation 4 2 Other f...

Страница 7: ...Installation preferably in closed metal tanks or pipes The sensor must be in electrical contact with the metal process connection When installed in plastic tanks there may be deterioration caused by...

Страница 8: ...ive and viscous media and media prone to sedimentation or build up the installation positions 1 are only suitable to some extent Residues might be detected as level 5 2 2 Unit types with long probe In...

Страница 9: ...unit in the system complies with EHEDG guidelines u Use self draining installation u Only use process adapters permitted according to EHEDG with special seals required by the EHEDG position paper The...

Страница 10: ...he thread using a suitable lubricating paste which has been approved for this application u Screw the sensor into the respective process connection and tighten it Maximum tightening torque 20 25 Nm u...

Страница 11: ...t hygienic zero leak using PEEK gasket 3 4 1 3 4 3 Fig 8 LMT seal PEEK 1 Green flat seal 3 PEEK sealing ring beige accessory E43323 4 Black flat seal E43323 u If needed replace green flat seal 1 on de...

Страница 12: ...Normal operation factory setting L 1 BN 2 WH 4 BK 3 BU OUT1 OUT2 L 4 3 2 1 Teach operation L 1 BN 2 WH 4 BK 3 BU IN OUT2 L 4 3 2 1 Pin Core colours 1 BN brown 2 WH white 3 BU blue 4 BK black OUT1 PNP...

Страница 13: ...nfiguration of the unit detailed information about process data structure diagnostic information parameter addresses and the necessary information about the required IO Link hardware and software can...

Страница 14: ...nimum hysteresis 2 Reference values Aqueous water based media SPx 62 rPx 54 Media with low water content SPx 35 rPx 29 Oils fats powders SPx 8 rPx 5 ou1 ou2 ou1 ou2 output function for OUT1 OUT2 Hno h...

Страница 15: ...he teach input The teach input must be activated u This requires previous configuration via IO Link parameter ou2 tch Output OUT2 must be configured as hysteresis function Hnc or Hno If the window fun...

Страница 16: ...ellow with 8 Hz w The unit returns to the operating mode with unchanged settings Possible faults Time error teach time too long too short Internal sensor signal not clear Wrong output function Paramet...

Страница 17: ...lure OFF OFF Teach operation Full adjustment via the teach input and Changing the output function Fault during the teach operation LEDs are flashing green yellow with 8Hz 1 according to the level The...

Страница 18: ...tant to ingress and without dead space u It is not possible to repair the unit u In case of return shipment ensure that the unit is free from soiling especially from dangerous and toxic substances u F...

Страница 19: ...y setting LMT0xA User settings SP1 8 rp1 5 ou1 Hno SP2 8 rp2 5 ou2 Hnc FOU1 OFF FOU2 OFF dS1 0 0 dS2 0 0 dr1 0 0 dr2 0 0 P n PnP dFo 0 0 Percentage values refer to the process value Parameter setting...

Отзывы: