Binary level sensor
LMT0xA
11
2
1
Fig. 7: LMT seal, metal-to-metal
1:
Green flat seal
2:
Metal sealing cone
u
Insert the green flat seal (1) and/or check its position.
u
If required: Lightly grease the thread using a suitable lubricating paste which has been approved
for this application.
u
Screw the sensor into the respective process connection and tighten it.
Maximum tightening torque: 20...25 Nm.
u
After installation check the tank / pipe for ingress resistance.
Flush mount hygienic zero-leak using PEEK gasket (3):
4
1
3
4
3
Fig. 8: LMT seal, PEEK.
1:
Green flat seal
3:
PEEK sealing ring beige (accessory E43323)
4:
Black flat seal (E43323)
u
If needed, replace green flat seal (1) (on delivery) with black flat seal (4). The flat seal (4) is
supplied with the article E43323!
u
Slide the PEEK sealing ring (3) onto the sensor tip until you feel the end stop (cone).
u
If required: Lightly grease the thread using a suitable lubricating paste which has been approved
for this application.
u
Screw the sensor into the respective process connection and tighten it.
Maximum tightening torque: 20...25 Nm.
u
After installation check the tank / pipe for ingress resistance.
GB