9
UK
►
Screw the sensor into the adapter until it
is hand-tight� Do not damage the sealing
chamfers�
►
Clamp sensor and adapter into a clamping
device (D). Tighten the clamping device
only slightly so that the adapter does not
warp. The sealing chamfers (E) must not be
damaged�
►
Tighten the sensor using a spanner until
you can feel the end stop (corresponding
to a maximum tightening torque of 25 Nm /
18 ftlb). Note: Do not overtighten. This can
have an adverse effect on the sealing�
NOTE: A guarantee for a long-term stable and maintenance-free fitting with no bug
traps in the hygienic sealing of the metal seal (Aseptoflex connection) is only valid
for once-only mounting�
Welding adapter
First weld the adapter, then mount the sensor� Follow the instructions included
with the adapter�
Use in hygienic areas to EHEDG
►
Make sure that the sensors are integrated into the system in accordance with
EHEDG.