3 Installation
Using process adapters the unit can be adapted to different process connections�
•
Adapters have to be ordered separately as accessories�
A correct fit of the unit and ingress resistance of the connection are only
ensured using ifm adapters. Mounting of the adapter → 3.3.
3.1 Installation location
General
•
The sensor tip is to be completely
surrounded by the medium�
• Insertion depth of the sensor:
minimum 12 mm�
Recommended
• For horizontal pipes: mounting from
the side�
• For vertical pipes: mounting in the
rising pipe�
Conditional
•
Horizontal pipe /mounting from
the bottom: if the pipe is free from
build-up�
•
Horizontal pipe /mounting from the
top: if the pipe is completely filled
with medium�
To avoid
•
The sensor tip must not be in
contact with the pipe wall�
• Do not mount in downpipes that are
open at the bottom!