![IFM efector300 SI6000 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/ifm/efector300-si6000/efector300-si6000_operating-instructions-manual_620727010.webp)
10
6.2 High flow adjustment (optional)
The unit determines the existing flow as normal flow and adapts the display repre-
sentation (all LEDs except the switch point LED light green).
►
Let the normal flow circulate in the installation�
►
Press the pushbutton and keep it pressed�
>
LED 9 lights, after approx. 5 s it flashes.
►
Release the pushbutton�
The unit is now adapted to your flow conditions� It passes into the operating mode,
the display should now show example 1�
Note: The adjustment affects the switch point: It is increased proportionally
(maximum up to LED 7).
7 Additional settings (optional)
7.1 Low flow adjustment
If the unit is used in media other than water, you should additionally adapt the unit
to the minimum flow�
Note: The following adjustment must only be carried out after the high flow adjust
-
ment�
►
Let the minimum flow circulate in the installation or ensure flow standstill�
►
Press the pushbutton
and keep it pressed�
>
LED 0 lights, after approx. 5 s it flashes.
►
Release the pushbutton� The unit adopts the new value and passes into the
operating mode�
7.2 Configure the switching output
The unit is delivered as normally open� In case of need you can change the output
to normally closed:
►
Press the pushbutton
for at least 15 s�
>
LED 0 lights, after approx. 5 s it flashes.
>
After 10 s the current setting is displayed: LEDs 5...9 light orange (= output
normally open)�
>
After approx. 15 s LEDs 0...4 flash orange.
►
Release the pushbutton� The output is changed to normally closed operation�
For a new changeover repeat the operation�
Содержание efector300 SI6000
Страница 1: ...Operating instructions Flow monitors SI6000 SI6100 SI6200 706053 00 06 2011 UK ...
Страница 13: ...13 UK 11 Scale drawing SI6000 1 LED bar display 2 set button 3 Aseptoflex thread ...
Страница 14: ...14 SI6100 1 LED bar display 2 set button 3 Aseptoflex thread ...
Страница 15: ...15 UK SI6200 1 LED bar display 2 set button 3 Aseptoflex thread ...
Страница 17: ...17 UK More information at www ifm com ...