8.3  Restore the factory setting (reset)

 

► Press the pushbutton   for at least 15 s�

 

> LED 9 lights, after approx� 5 s it flashes�

 

> After approx� 15 s LEDs 0���9 flash orange� 

 

► Release the pushbutton� All settings are reset to the factory setting:

 -operating area: 5 ���100 cm/s for water

 -switch point: LED 7

 -output function: NO

 -unlocked�

8.4  Lock / unlock the unit

The unit can be locked electronically to prevent unintentional settings�

 

► Press both setting pushbuttons simultaneously for at least 10 s in the operating 

mode� 

 

> The indication goes out, the unit locks or unlocks� 

On delivery: unlocked�

8.5  Remote adjustment

You can adapt the unit to new flow conditions any time�

•  Apply the operating voltage for > 5 ��� < 10 s to Pin 2 = high flow adjustment�

•  Apply the operating voltage for > 10 ��� < 15 s to Pin 2 = low flow adjustment�

This adjustment does not affect the switch point (the relative position is not chan-

ged)�

9  Error during adjustment

If no adjustment is possible, all LEDs flash red� The unit then passes into the 

operating mode with unchanged values�

Possible cause /aid:

Error during installation�

 

► Read chapter 4 Installation� 

Check whether all requirements have 

been met�

The difference between maximum flow and 

minimum flow is too small�

 

► Increase the flow difference and carry 

out the adjustment once again�

The sequence high flow /low flow adjust-

ment was not adhered to�

 

► Carry out the two adjustment operations 

again in the right sequence�

Содержание efector 300 SI5010

Страница 1: ...Operating instructions Flow monitors SI5010 704621 01 08 2010 UK...

Страница 2: ...4 3 Mounting operation 6 5 Electrical connection 7 6 Operating and display elements 7 7 Set up and settings for water 8 7 1 Change the switch point optional 8 7 2 High flow adjustment optional 9 8 Add...

Страница 3: ...n prior to set up of the unit Ensure that the product is suitable for your application without any restrictions The unit conforms to the relevant regulations and EC directives Improper or non intended...

Страница 4: ...ng status changes if the value SP minus hysteresis is reached The hysteresis changes with the flow speed and it is essentially influenced by the set monitoring range It is 2 5 cm s for the setting 5 1...

Страница 5: ...lation location General The sensor tip is to be completely surrounded by the medium Insertion depth of the sensor minimum 12 mm Recommended For horizontal pipes mounting from the side For vertical pip...

Страница 6: ...rces of interference 4 3 Mounting operation Ensure that the system is free of pressure during installation Ensure that no media can leak at the mounting location during installa tion Grease the thread...

Страница 7: ...4 2 1 3 4 1 3 2 Teach L L OUT1 Data OUT1 Data switching signal for flow limit value and data channel for bidirectional communication Teach input for teach signal 6 Operating and display elements 1 Ope...

Страница 8: ...2 3 Your normal flow exceeds the representation range of the display LED 9 flashes Carry out high flow adjustment 6 2 You can restore the factory setting any time 8 3 7 1 Change the switch point optio...

Страница 9: ...you should additionally adapt the unit to the minimum flow Note The following adjustment must only be carried out after the high flow adjust ment Let the minimum flow circulate in the installation or...

Страница 10: ...adapt the unit to new flow conditions any time Apply the operating voltage for 5 10 s to Pin 2 high flow adjustment Apply the operating voltage for 10 15 s to Pin 2 low flow adjustment This adjustment...

Страница 11: ...the representation range LED 0 flashes current flow far below the represen tation range Interference indicator Short circuit at the switching output The operating indicator and red LEDs light alterna...

Страница 12: ...13 Technical data Application area Liquids and gases Operating voltage V 19 36 DC1 Current rating mA 250 Short circuit protection pulsed reverse polarity overload protection Voltage drop V 2 5 Curren...

Страница 13: ...ating IP 67 Protection class III Shock resistance g 50 DIN IEC 68 2 27 11 ms Vibration resistance g 20 DIN IEC 68 2 6 55 2000 Hz Housing materials stainless steel 316L 1 4404 stainless steel 304 1 430...

Отзывы: