• If the level is below SP1, output 1 switches. If SP1 is exceeded or if
there is a wire break, output 1 switches off (alarm).
• If the level reaches SP2, the output 2 provides a signal (upper preset
value reached, finish refilling).
• If the level is below SP3, the output 3 provides a signal (below lower
preset value, start refilling).
• If the level is above SP4, the output is switched. If the level is below
SP4 or if there is a wire break, output 4 switches off (alarm message
"below min. value/wire break").
Storage vessel
Monitoring of the
acceptable range
(alarm) and level
control with 4
switching outputs
(
bin
=
OFF
)
Replaces 4
float switches
Page 33
ENGLISH
t
L
SP1
SP2
1
0
OFS
OUT1
Hnc
1
0
OUT2
Hno
SP3
SP4
1
0
OUT3
Hnc
1
0
OUT4
Hno
display value
Configuration of the switching outputs 1 ... 4 (bin = OFF)
max. value exceeded
→
alarm
hysteresis function, normally closed (
Hnc
)
...
upper preset value reached
→
finish refilling
hysteresis function, normally open (
Hno
)
below lower preset value
→
start refilling
hysteresis function, normally closed (
Hnc
)
below min. value
→
alarm
hysteresis function, normally open (
Hno
)
each slightly below SPx, (to suppress wave movements) (preset)